EVCO EVB1256N9D User Manual
Page 52

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 52 of 92
d15
0
99
min
0
0
0
0
0
0
0
0
minimum time that the compressor must be switched on
before defrosting can be activated (only if d1 = 1) (18)
d16
0
99
min
0
0
0
0
0
0
0
0
predripping duration (during predripping the compressor
will remain switched off, the defrosting output will be
activated and the evaporator fan will remain switched off)
d18
0
999
min
40
40
40
40
40
40
40
40
defrosting interval (only if d8 = 3; defrosting will be
activated when the compressor has been on totally, with
the evaporator temperature below that of d22, for time
d18)
0
=
defrosting will never be activated due to the effect
of this condition
d19
0.0
40.0
°C/°F
(1)
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
evaporator temperature above which the defrost is
activated (relative to the evaporator temperatures
average, or “evaporator temperatures average - d19”)
(only if d8 = 3)
d20
0
500
min
180
180
180
180
180
180
180
180
minimum consecutive time the compressor must be
switched on such as to provoke the defrost activation
0
=
defrosting will never be activated due to the effect
of this condition