EVCO EVB1256N9D User Manual
Page 48

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 48 of 92
C14
0
2
- - - -
0
0
0
0
0
0
2
2
type of pump down
0
=
TIMED - the compressor and the pump down
valve (or the electronic expansion valve if
present) shall be switched on at the same time
due to the setting; the pump down valve (or the
electronic expansion valve if present) shall be
turned off due to the setting and the compressor
after the expiration of the u3 time interval from
the valve switch-off (only if u1 and/or u11 = 10)
1
=
FROM DIGITAL INPUT - the compressor and the
pump down valve (or the electronic expansion
valve if present) shall be switched on at the same
time due to the setting; the pump down valve
shall be turned off due to the setting and the
compressor afterwards and as a consequence of
the activation of the multifunction or multifunction
2 input (only if i5 or i15 = 6); see also u3 (only if
u1 and/or u11 = 10)
2
=
FOR
EVAPORATING
PRESSURE
-
(ONLY
AVAILABLE IN MODELS EVB1246 and EVB1256) -
the electronic expansion valve (it will also work as
pump down valve) will be switced-on due to the
setting and the compressor on afterwards; the
electronic expansion valve will be switched off due
to the setting and the compressor on afterwards
and as a consequence of the attainment by the
evaporating pressure of the value set with
parameter h10; see also u3