C14

0

2

- - - -

0

0

0

0

0

0

2

2

type of pump down

0

=

TIMED - the compressor and the pump down

valve (or the electronic expansion valve if

present) shall be switched on at the same time

due to the setting; the pump down valve (or the

electronic expansion valve if present) shall be

turned off due to the setting and the compressor

after the expiration of the u3 time interval from

the valve switch-off (only if u1 and/or u11 = 10)

1

=

FROM DIGITAL INPUT - the compressor and the

pump down valve (or the electronic expansion

valve if present) shall be switched on at the same

time due to the setting; the pump down valve

shall be turned off due to the setting and the

compressor afterwards and as a consequence of

the activation of the multifunction or multifunction

2 input (only if i5 or i15 = 6); see also u3 (only if

u1 and/or u11 = 10)

2

=

FOR

EVAPORATING

PRESSURE

-

(ONLY

AVAILABLE IN MODELS EVB1246 and EVB1256) -

the electronic expansion valve (it will also work as

pump down valve) will be switced-on due to the

setting and the compressor on afterwards; the

electronic expansion valve will be switched off due

to the setting and the compressor on afterwards

and as a consequence of the attainment by the

evaporating pressure of the value set with

parameter h10; see also u3