EVCO EVB1256N9D User Manual
Page 41

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 41 of 92
P1
0
1
- - - -
1
1
1
1
1
1
1
1
degree Celsius decimal point
1
=
YES
P2
0
1
- - - -
0
0
0
0
0
0
0
0
temperature unit of measurement (2)
0
=
degree Celsius
1
=
degree Fahrenheit
P3
0
2
- - - -
1
1
1
1
1
1
1
1
evaporator temperature probe function
0
=
probe absent
1
=
defrosting probe and probe for evaporator fan
thermostating
2
=
probe for evaporator fan thermostating
P4
0
4
- - - -
3
3
3
3
3
3
3
3
magnitude recorded by the auxiliary temperature probe
0
=
probe absent
1
=
condenser temperature
2
=
critical temperature
3
=
evaporator 2 temperature
4
=
outlet
air
temperature;
in
this
case
the
temperature associated with the setting shall be
the CPT (Calculated Product Temperature) one;
see also P7
P5
0
4
- - - -
0
0
0
0
0
0
0
0
magnitude displayed during normal operation
0
=
if P4 = 0, 1, 2 or 3, room temperature
if P4 = 4, CPT temperature
1
=
working set-point
2
=
evaporator temperature
3
=
temperature recorded by the auxiliary probe (see
P4)
4
=
inlet air temperature (only if P4 = 4 )