EVCO EVB1256N9D User Manual
Page 46

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 46 of 92
PARAM.
MIN.
MAX.
M.U.
E
V
B
1
2
0
4
E
V
B
1
2
1
4
E
V
B
1
2
0
6
E
V
B
1
2
1
6
E
V
B
1
2
2
6
E
V
B
1
2
3
6
E
V
B
1
2
4
6
E
V
B
1
2
5
6
COMPRESSOR PROTECTION SYSTEM
C0
0
240
min
0
0
0
0
0
0
0
0
delay in switching on of compressor after the device
switches on (8)
C1
0
240
min
5
5
5
5
5
5
5
5
minimum time between two consecutive compressor
start-ups; also delay in compressor start-up after
conclusion of room temperature/inlet air probe error
(code “Pr1”) (9) (10)
C2
0
240
min
3
3
3
3
3
3
3
3
minimum compressor switch-off duration (9)
C3
0
240
s
0
0
0
0
0
0
0
0
minimum duration of compressor switch on time
C4
0
240
min
10
10
10
10
10
10
10
10
duration of compressor switch off time during a room
temperature/inlet air probe error (code “Pr1”); see also
C5
C5
0
240
min
10
10
10
10
10
10
10
10
duration of compressor switch on time during a room
temperature/inlet air probe error (code “Pr1”); see also
C6
C6
0.0
199
°C/°F (1)
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
condenser temperature is higher than that at which the
condenser overheating alarm is activated (code “COH”)
(11)
C7
0.0
199
°C/°F (1)
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
condenser
temperature
above
which
the
blocked
compressor alarm is activated (code “CSd”)