Table B-2: C-More Status and Fault Messages - Continued

CODE

MESSAGE

DESCRIPTION

39

DIRECT DRIVE

SIGNAL FAULT

The direct drive signal is not present or is out of range.

40

REMOTE SETPT

SIGNAL FAULT

The remote setpoint signal is not present or is out of range.

41

OUTDOOR TEMP

SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out of

range.

42

OUTLET TEMP

SENSOR FAULT

The temperature measured by the Outlet Sensor is out of

range.

43

FFWD TEMP

SENSOR FAULT

The temperature measured by the FFWD Sensor is out of

range.

44

HIGH WATER

TEMPERATURE

The temperature measured by the Outlet Sensor exceeded the

Temp Hi Limit setting.

45

LINE VOLTAGE

OUT OF PHASE

The High AC voltage is out of phase from the low AC voltage.

46

STEPPER MOTOR

FAILURE

The stepper motor failed to move the valve to the desired

position.

47

SETPT LIMITING ACTIVE

Setpoint temperature has exceeded the maximum allowable

setting.

48

MODBUS COMM FAULT

The RS485 (Modbus) network information is not present or is

corrupted.

49

BOILER_RETRY_WAIT_ME

SSAGE,

50

BOILER_FAULT_PURGE_M

ESSAGE,

51

BOILER_RETRY_PAUSE_M

ESSAGE,

52

EXHAUST_TEMP_SENSOR

_SHORT_MESSAGE,

53

EXHAUST_TEMP_SENSOR

_OPEN_MESSAGE,

54

EXHAUST_TEMP_HIGH_W

ARNING_MESSAGE,

55

EXHAUST_TEMP_HIGH_FA

ULT_MESSAGE,

56

INLET_TEMP_SENSOR_SH

ORT_MESSAGE,

57

INLET_TEMP_SENSOR_OP

EN_MESSAGE,