MC2: 04/23/13 Page 85 of 144

GF-131

AERCO Control System (ACS)

Installation, Operation, and Maintenance Manual

OMM-0081_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

APPENDIX A: ACS MENUS

Table A-1: ACS Menus

MENU LEVEL & OPTION

AVAILABLE CHOICES OR LIMITS

DEFAULT

MINIMUM

MAXIMUM

OPERATING MENU

HEADER TEMP

40

280

N/A

HEADER SET TEMP

40

220

N/A

OUTSIDE AIR TEMP

-60

180

N/A

PERCENT OF LOAD

0

100

N/A

I/O STATUS



See Appendix B

RETURN TEMP

(Displayed Only If

RETURN SENSOR MODE =

NORMAL or DHW/TANK TEMP)

40

280

N/A

OUTLET TEMP

(Displayed Only If

BOILER CONTROL SELECT =

CMORE or BCM)

40

280

N/A

ERROR/STATUS CODE

(Displayed Only If

BOILER CONTROL SELECT =

CMORE or BCM)

See App. B

See App. B

N/A

SETUP MENU

ENTER PASSWORD

(Level 1 = 159) (Level 2 = 6817)

0

32000

0

SET MONTH

01

12

SET DATE

01

31

SET YEAR

00

99

SET HOUR

00

23

SET MINUTE

00

59

SET DAY OF WEEK

SUNDAY TO SATURDAY

LSD:

Bit 0 = AUX Relay

Bit 1 = Fault Relay

Bit 2 = Sys Start Relay

Bit 3 = Empty

MSD:

Bit 0 = Setback

Bit 1 = Interlock 2

Bit 2 = Interlock 1

Bit 3 = Empty