Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual
Page 139

MC2: 04/23/13 Page 139 of 144
GF-131
AERCO Control System (ACS)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Installation, Operation, and Maintenance Manual
OMM-0081_0D
Table H-2: ACS Standard Holding Register Address Mapping - Continued
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
94 (0x005E) Net Boiler 3 Address Address for Network Boiler 3
Default = 0
95 (0x005F) Net Boiler 4 Address Address for Network Boiler 4
Default = 0
96 (0x0060) Net Boiler 5 Address Address for Network Boiler 5
Default = 0
97 (0x0061) Net Boiler 6 Address Address for Network Boiler 6
Default = 0
98 (0x0062) Net Boiler 7 Address Address for Network Boiler 7
Default = 0
99 (0x0063) Net Boiler 8 Address Address for Network Boiler 8
Default = 0
100 (0x0064) Net Boiler 9 Address Address for Network Boiler 9
Default = 0
101 (0x0065) Net Boiler 10
Address
Address for Network Boiler 10
Default = 0
102 (0x0066) Net Boiler 11address Address for Network Boiler 11
Default = 0
103 (0x0067) Net Boiler 12
Address
Address for Network Boiler 12
Default = 0
104 (0x0068) Net Boiler 13
Address
Address for Network Boiler 13
Default = 0
**105 (0x0069) Net Boiler 14
Address
Address for Network Boiler 14
Default = 0
106 (0x006A) Net Boiler 15
Address
Address for Network Boiler 15
Default = 0
107 (0x006B) Net Boiler 16
Address
Address for Network Boiler 16
Default = 0
108 (0x006C) Net Boiler 17
Address
Address for Network Boiler 17
Default = 0
109 (0x006D) Net Boiler 18
Address
Address for Network Boiler 18
Default = 0
110 (0x006E) Net Boiler 19
Address
Address for Network Boiler 19
Default = 0
111 (0x006F) Net Boiler 20
Address
Address for Network Boiler 20
Default = 0