Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual
Page 129

MC2: 04/23/13 Page 129 of 144
GF-131
AERCO Control System (ACS)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Installation, Operation, and Maintenance Manual
OMM-0081_0D
Table H-1: ACS Standard Input Register Address Mapping - Continued
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
39 (0x0027) Boiler 15 Status
(Net Boiler 15)
119 = Not On-Line
120 = On-Line But Not Fired
1–40 = Fired & Sequence
121 = On-Line But Disabled
122 = On-Line But Faulted
40 (0x0028) Boiler 16 Status
(Net Boiler 16)
Same As Above
41 (0x0029) Boiler 17 Status
(Net Boiler 17)
Same As Above
42 (0x002A) Boiler 18 Status
(Net Boiler 18)
Same As Above
43 (0x002B) Boiler 19 Status
(Net Boiler 19)
Same As Above
44 (0x002C) Boiler 20 Status
(Net Boiler 20)
Same As Above
45 (0x002D) Boiler 21 Status
(Net Boiler 21)
Same As Above
46 (0x002E) Boiler 22 Status
(Net Boiler 22)
Same As Above
47 (0x002F) Boiler 23 Status
(Net Boiler 23)
Same As Above
48 (0x0030) Boiler 24 Status
(Net Boiler 24)
Same As Above
49 (0x0031) Boiler 25 Status
(Net Boiler 25)
Same As Above
50 (0x0032) Boiler 26 Status
(Net Boiler 26)
Same As Above
51 (0x0033) Boiler 27 Status
(Net Boiler 27)
Same As Above
52 (0x0034) Boiler 28 Status
(Net Boiler 28)
Same As Above
53 (0x0035) Boiler 29 Status
(Net Boiler 29)
Same As Above
54 (0x0036) Boiler 30 Status
(Net Boiler 30)
Same As Above