Table A-1: ACS Menus - Continued
MENU LEVEL & OPTION
AVAILABLE CHOICES OR LIMITS
DEFAULT
MINIMUM
MAXIMUM
CONFIGURATION MENU
BOILER CONTROL SELECT
OFF, CMORE, BCM
OFF
BOILER OP MODE
SEQUENTIAL MODE,
PARALLEL MODE
SEQUENTIAL
MODE
SYS INTLK CONFIG
START ENABLED,
ALWAYS ENABLED
START ENABLED
BLR START LEVEL
001%
100%
020%
BLR STOP LEVEL
001%
040%
016%
MAX POWER INPUT
050%
100%
100%
FAIL SAFE MODE
SHUTDOWN,
CONSTANT SETPOINT
SHUTDOWN
LEAD BOILER SELECT
NONE, NETW BOILER 1
NONE
LAST BOILER SELECT
NONE, NETW BOILER 1,
NETW BOILER 2, Etc., Up To:
NETW BOILER 32
NONE
ROTATE TIME
0 to 999 HOURS
168 HOURS
RETURN SENSOR MODE
OFF, NORMAL, DHW/TANK TEMP
OFF
PLANT DELTA-T LIMIT
10°F TO 100°F
40°F
BOILER DELAY
10 TO 999 SEC
30 SEC
DHW OPTION
OPTION 1, OPTION 2, OPTION 3,
NO OPTION
NO OPTION
NUMBER OF DHW BOILERS
(Displayed Only if
DHW OPTION = 1 or 2)
0 to 8
1
DHW SIGNAL
(Displayed Only if DHW OPTION = 1
or 2)
NO SIGNAL, SPECIAL SIGNAL
NO SIGNAL
VALVE WAIT STATE
(Displayed Only if
DHW OPTION = 1 or 2)
OFF, ON
OFF
SYSTEM RELAY OPTION
(Displayed Only if DHW OPTION = 1)
NORMAL, DHW VALVE 1
DHW VALVE 1
NUMBER OF DHW PRIORITY BLRS
(Displayed Only if DHW OPTION = 2)
0 TO (NUM DHW BLRS – 1)
0
BOOST TEMP
(Displayed Only if DHW OPTION = 3)
40°F TO 200°F
140°F
RETURN TEMP BOOST DISABLE
-10°F TO 10°F
0°F