beautypg.com

3 outdoor air sensor installation, Outdoor air sensor installation, Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 20

background image

MC2: 04/23/13 Page 20 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

PROBE DEPTH MUST

EXTEND AT LEAST 2"

INTO PIPE

WELDED 1/2"

COUPLING OR

4"x4*x1/2"

T - FITTING

HEADER SENSOR

WITH THERMOWELL

INSTALLED

Figure 2-3: Header Sensor Installation Details

2.5.3 Outdoor Air Sensor Installation

The Outdoor Air Temperature Sensor (part no. GP-122662) is required when operating in the

ACS in the Outdoor Reset Mode (paragraph 4.2). An Outdoor Air Sensor Kit (part no. GM-

122781) is also available. This kit contains the Sensor (GP-122662) and a Mounting Bracket for

wall mounting. The Outdoor Air Sensor should be mounted on the North side of the building,

shielded from direct sunlight, and away from air intakes or outlets from the building. Shielded

pair 18 AWG cable (Belden # 8760 or equiv.) is recommended for sensor wiring. The Outdoor

Air Sensor can be mounted up to 600 feet from the ACS. See instructions below.

NOTE

The Outdoor Air Sensor is a thermistor type sensor. The Resistance vs.

Temperature Chart for this sensor is provided in

Appendix E. Length of

Header Sensor wire leads should not exceed 600 feet.









Outdoor Air Sensor Installation

1. Refer to

Figure 2-4 for a typical Outdoor Air Sensor installation.

2. Attach the sensor to the mounting bracket and secure the bracket in a suitable location

on the North side of the building.

3. Using shielded pair cable (Belden #8760 or equiv.), connect the two Sensor leads to

terminals 1 and 2 on the ACS. There is no polarity to observe when connecting the

sensor.

4. Terminate the cable shield at SHLD terminal 3 of the ACS. DO NOT terminate the shield

at the Sensor end of the cable.