Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 125

background image

MC2: 04/23/13 Page 125 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table G-4: ACS Commands - Continued

No.

COMMAND

ENTRY RANGE

FACTORY DEFAULT

129

Modbus Pass-Thru

0 = Disabled

1 = Enabled

0 = Disabled

130

Header Temp Deadband

01 to 15°F

05°F

131

Outside Temp Sensor Offset

-10.0°F to 10.0°F

0.0°F

132

Ramp Up %/Min

000 to 300

20

133

Ramp Down %/Min

000 to 300

200

134

Fault Alarm Boilers

No Blr Faults

All Blr faults

No Blr Faults

135

4-20 mA Offset

-1.00 to 1.00 mA

0.0 mA

136

Return Sensor Offset

-10.0 to 10.0°F

0.0°F

137

Load Start Pct

000 to 100

1

138

Load Stop Pct

000 to 100

0

150

I/O Status

00 to 255

Bit 0 = AUX Relay

Bit 1 = Fault Relay

Bit 2 = Sys Start Relay

Bit 3 = Empty

Bit 4 = Setback

Bit 5 = Interlock 2

Bit 6 = Interlock 1

Bit 7 = Empty

151

&

Up

(Reserved For Future Expansion)

Undefined