beautypg.com

2 rs485 wiring for modulex series boilers, Rs485 wiring for modulex series boilers, Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 29: Bcm front view

background image

MC2: 04/23/13 Page 29 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

2.7.2 RS485 Wiring for Modulex Series Boilers

RS485 wiring connections are made at the MODBUS terminals of each Boiler’s BCM Module as

shown in

Figure 2-9. Connect the wiring as shown below:















Y2

Y3

Y4

Y1

SW1

A1

I

0

BCM FRONT VIEW

7 6 5 4 3 2 1

Y2

JP2

JP1

T

C
V

JUMPER

SHOWN IN

“TERMINATED”

(UP) POSITION

MODBUS B

(+)

MODBUS A

(-)

Figure 2-9: RS485 (Modbus) Wiring For Modulex Series Boilers

RS485 Wiring at Boiler BCM of Modulex Boiler(s)

1. Connect the positive lead to terminal

1 (MODBUS B +) of connector Y2.

2. Connect the negative lead to terminal

2 (MODBUS A -) of connector Y2.

3. DO NOT terminate the shields at the Boiler end of the RS485 loop.

Connect the shields of the incoming and outgoing leads together. The

RS485 loop shield should only be terminated at the ACS.

4. The last BCM in the daisy-chain must have the termination jumper

engaged as shown in

Figure 2-9.

5. The two ACS bias switches (

Figure 2-6) must be activated by placing them

in the down position.