Table H-2: ACS Standard Holding Register Address Mapping - Continued

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

52 (0x0034) Offset On Time Day 1 – Hours 00 to 23 Hours

Default = 0

53 (0x0035) Offset On Time Day 2 – Hours 00 to 23 Hours

Default = 0

54 (0x0036) Offset On Time Day 3 – Hours 00 to 23 Hours

Default = 0

55 (0x0037) Offset On Time Day 4 – Hours 00 to 23 Hours

Default = 0

56 (0x0038) Offset On Time Day 5 – Hours 00 to 23 Hours

Default = 0

57 (0x0039) Offset On Time Day 6 – Hours 00 to 23 Hours

Default = 0

58 (0x003A) Offset On Time Day 7 – Hours 00 to 23 Hours

Default = 0

59 (0x003B) Offset Enable

0 or 1

0 = Disabled

1 = Enabled

Default = 0

(Disabled)

60 (0x003C) Header Temp Offset

-10 to 10°F

Default = 0°F

61 (0x003D) System Start Interlock

1, 2 or 3

1 = Intlk1 Opens Start Relay

2 = Intlk2 Opens Start Relay

3 = Either Intlk Opens Start

Relay

Default = 1

(Intlk 1)

62 (0x003E)

Thru

69 (0x0045)

(Reserved)

70 (0x0046) Offset Off Time Sun. –

Minutes

0 to 59 Minutes

Default = 0

71 (0x0047) Offset Off Time Mon. –

Minutes

0 to 59 Minutes

Default = 0

72 (0x0048) Offset Off Time Tue.– Minutes 0 to 59 Minutes

Default = 0

73 (0x0049) Offset Off Time Wed.–

Minutes

0 to 59 Minutes

Default = 0

74 (0x004A) Offset Off Time Thu – Minutes 0 to 59 Minutes

Default = 0

75 (0x004B) Offset Off Time

Fri. – Minutes

0 to 59 Minutes

Default = 0