beautypg.com

Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 130

background image

MC2: 04/23/13 Page 130 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table H-1: ACS Standard Input Register Address Mapping - Continued

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

55 (0x0037) Boiler 31 Status

(Net Boiler 31)

119 = Not On-Line

120 = On-Line But Not Fired

1–40 = Fired & Sequence

121 = On-Line But Disabled

122 = On-Line But Faulted

56 (0x0038) Boiler 32 Status

(Net Boiler 32)

Same As Above

57 (0x0039) I/O Status

00 to 255

Bit map of

Input/Output Status:

LSD:

Bit 0 = AUX Relay

Bit 1 = Fault Relay

Bit 2 = Sys Start

Relay

Bit 3 = Empty

MSD:

Bit 4 = Setback

Bt 5 = Interlock 2

Bit 6 = Interlock 1

Bit 7 = Empty

See Appendix A,

Table A-7.

58 (0x003A) Return Sensor Temp 40°F to 220°F

When Ret Sensor

Mode = Normal

59 (0x003B) Net Blr 1 Outlet Temp 40°F to 220°F

When Blr Cntl Type =

1 or 2

60 (0x003C) Net Blr 2 Outlet Temp 40°F to 220°F

61 (0x003D) Net Blr 3 Outlet Temp 40°F to 220°F

62 (0x003E) Net Blr 4 Outlet Temp 40°F to 220°F

63 (0x003F) Net Blr 5 Outlet Temp 40°F to 220°F

64 (0x0040) Net Blr 6 Outlet Temp 40°F to 220°F

65 (0x0041) Net Blr 7 Outlet Temp 40°F to 220°F

66 (0x0042) Net Blr 8 Outlet Temp 40°F to 220°F

67 (0x0043) Net Blr 9 Outlet Temp 40°F to 220°F

68 (0x0044) Net Blr 10 Outlet Temp 40°F to 220°F