beautypg.com

1 system start relay, 2 fault alarm relay, 3 auxiliary relay – AERCO Control System (ACS) User Manual

Page 33: 13 4-20 ma wiring, 14 mounting and wiring the optional acs relay box, System start relay, Fault alarm relay, Auxiliary relay, Gf-131 aerco control system (acs)

background image

MC2: 04/23/13 Page 33 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

NOTE

The state of the SYS START, FLT ALARM and AUX Relays are

controlled by options contained in the Relay Menu described in

Chapter 3, paragraph 3.11.

2.12.1 System Start Relay

The state of the System Start (SYS START) relay contacts are controlled by the value set for

the SYS START TEMP and SYS START OPTION in the Relay Menu. The contacts are closed

either when the outdoor air temperature is less than the System Start Temperature (SYS

START TEMP) or when there is a load, or both. The default value for this temperature setting is

70°F. See

paragraph 4.5 for additional information.

2.12.2 Fault Alarm Relay

The state of the Fault Alarm (FLT ALARM) relay contacts are controlled by the option selected

for the FAULT ALRM RELAY, FAULT ALARM BLR and FAULT ALRM CLEAR in the Relay

Menu. Contact closure can be set to: ALL FAULTS, NO INTERLOCK, INTERLOCK 2 or

INTERLOCK 1. The default for this option is ALL FAULTS.

2.12.3 Auxiliary Relay

The state of the Auxiliary (AUX) relay contacts are controlled by the AUX RELAY CLOSE and

AUX RELAY OPEN options selected in the Relay Menu. Contact closure can be set to occur

either when all available boilers are at the 100% Fire Rate or for either when all boilers are at

100% Fire Rate or no boilers are available (all boilers faulted or turned off).

2.13 4-20 MA WIRING

The ACS can accept a remote 4 – 20 mA current signal representing a setpoint. This input is

fused internally at 0.63A. Connect the signal leads to the 4-20 + and 4–20 – terminals. Refer to

Chapter 4, paragraph 4.3 for Remote Setpoint programming using a 4 -20 mA input.

2.14 MOUNTING AND WIRING THE OPTIONAL ACS RELAY BOX

The ACS (Aerco Control System) Relay Panel is used in combination with the ACS to control up

to 2 isolation valves, boiler interlocks, and a Domestic Hot Water (DHW) pump in a Combination

heating plant where AERCO boilers are bring used for both Building Heat and Domestic Hot

Water heating.

Figure 2-13: AERCO Control System (ACS) Relay Box