Table C-7: Header Temperature for a Building Reference Temperature of 90°F
RESET RATIO
Air
Temp
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
90°F
90°F
90°F
90°F
90°F
90°F
90°F
90°F
90°F
90°F
90°F
85°F
93°F
94°F
95°F
96°F
97°F
98°F
99°F
100°F 101°F 102°F
80°F
96°F
98°F
100°F 102°F 104°F
106°F
108°F 110°F 112°F 114°F
75°F
99°F
102°F 105°F 108°F 111°F
114°F
117°F 120°F 123°F 126°F
70°F 102°F 106°F 110°F 114°F 118°F
122°F
126°F 130°F 134°F 138°F
65°F 105°F 110°F 115°F 120°F 125°F
130°F
135°F 140°F 145°F 150°F
60°F 108°F 114°F 120°F 126°F 132°F
138°F
144°F 150°F 156°F 162°F
55°F 111°F 118°F 125°F 132°F 139°F
146°F
153°F 160°F 167°F 174°F
50°F 114°F 122°F 130°F 138°F 146°F
154°F
162°F 170°F 178°F 186°F
45°F 117°F 126°F 135°F 144°F 153°F
162°F
171°F 180°F 189°F 198°F
40°F 120°F 130°F 140°F 150°F 160°F
170°F
180°F 190°F 200°F 210°F
35°F 123°F 134°F 145°F 156°F 167°F
178°F
189°F 200°F
30°F 126°F 138°F 150°F 162°F 174°F
186°F
198°F 210°F
25°F 129°F 142°F 155°F 168°F 181°F
194°F
207°F
20°F 132°F 146°F 160°F 174°F 188°F
202°F
216°F
15°F 135°F 150°F 165°F 180°F 195°F
210°F
10°F 138°F 154°F 170°F 186°F 202°F
218°F
5°F
141°F 158°F 175°F 192°F 209°F
0°F
144°F 162°F 180°F 198°F 216°F