Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table 5-2: Common Problems

Problem

Possible Causes

Solution

Boiler plant not started

by ACS

ACS not turned ON.

Outside air temperature higher

than system’s start

temperature

Configuration not correct.


System must be initialized

Wiring between boilers and

ACS not correct

Press ON/OFF button and ensure that

the LED lights

Check outside air temperature and

system start temperature. System start

temperature should be higher than

outside air temperature for boilers to

run. Check SYS START TEMP setting

in RELAY MENU (paragraph 3.11).

Check SYS START OPTION in RELAY

MENU. Load START PCT and STOP

PCT in CALIBRATION MENU

paragraphs 3.11, 3.12).

Initialize and test system (para. 4.7 and

4.8).

Check wiring. (See Chapter 2 &

Appendix E)

BMK or KC Boiler with

C-More Control Box not

being recognized by

ACS.

C-More Box not configured

correctly.

C-More Box not enabled. Front

panel switch is off.

Incorrect wiring between ACS

and Boiler.

Alarm condition present on C-

More Control Box.

Ensure that the C-More Boiler is

configured for Direct Drive (see

Chapter 5 of correct BMK or KC1000

O & M Manual for required menu

settings).

Check ON/OFF switch.

See Chapter 2 for correct wiring

connections

Clear alarm condition.

Modulex Boiler with

BCM Control not being

recognized by ACS.

BCM not configured correctly.

3-position switch on boiler not

in correct position.

BCM Control is in alarm.

Incorrect wiring between ACS

and BCM Control.

Ensure that last boiler has termination

activated (see GF-114, GF-115-C).

Ensure that the 3-position switch is in

the 0 (zero) position.

Clear alarm condition.

Refer to Chapter 2 for correct wiring

connections.

ACS controlling boilers.

EMS can see ACS, but

cannot see boilers.

MODBUS PASS THRU not

enabled in ACS.

EMS communication response

time too short.

See RS232 MENU (paragraph 3.6).

Allow at least 2 seconds to receive

boiler information.