beautypg.com

17 relay panel operation, Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 40

background image

MC2: 04/23/13 Page 40 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

2.17 RELAY PANEL OPERATION









Figure 2-15: ACS Relay Panel Front Panel

The board operates basically as follows:

a) In the normal idle state, all the inputs, except one of the Valve End Switch In inputs, would

be open. As a result, the Aquastat Out would be open and the Valve End Switch Out would

be closed. All the relays except the Interlocks Relay will be in their unpowered state – DHW

Pump off, Valve 1 closed(N.C. powered), and Valve 2 open (N.C. powered). Since the

Valve End Switch Output would be activated, all the Interlocks relays will be activated and

all its contacts closed thereby enabling the Building Priority boilers to run if needed.

NOTE

If no Valve 2 (Sys Relay) is used, the Interlocks Relay connection

will not need to be used.

b) When the tank calls for heat and the Aquastat Input closes, the DHW Pump relay will

activate. The ACS will activate Valve 1 to close if it is not already closed. Once closed the

ACS will allow the DHW Priority boilers to run to provide heat to the tank.
If all the DHW Priority boilers are running at 100% for more than 2 minutes, the ACS will

open Valve 1 and close Valve 2 and activate the Building Priority boilers to help with DHW

heating.
When the Aquastat Input opens, the DHW Pump will turn off after some time delay (currently

60 seconds). The DHW Priority boilers will also shut down and Valve 1 will close and Valve

2 open.

c) Generally if any of the two valves is fully open and its Valve End Switch Input closes, the

Interlock relays will activate to allow the Building Priority boilers to run. When the Valve End

Switch Input opens, the Interlock relays will de-activate.

d) The Valve 1 Relay output is labeled such that the Normally Closed (N.C.) contact is Valve 1

Close and the Normally Open (N.O.) contact is Valve 1 Open. The Valve 2 Relay output is

labeled such that the Normally Closed (N.C.) contact is Valve 2 Open and the Normally

Open (N.O.) contact is Valve 2 Close. It is important to make these connections correctly. In

this way, the unpowered state of the relay panel will keep the valves in the default state with

Valve 1 closed and Valve 2 open.

Clear Plastic

Cover

Wiring Compartment Cover

Front Panel