3.14.1 CONSTANT SETPT MODE (Default):
MENU & OPTION
ACTION
1. SETUP MENU
ENTER PASSWORD
Enter 159
2. RS485 MENU
Enter this menu if there are more than 2 boilers (default), otherwise go to
step 3
NUMBER NETW
BOILERS
This setting is preset to 2. If more than 2 Boilers (default), enter number
(03, 04, etc)
NETW BOILER 01
ADDRESS= 001
Address 001 and 002 are preset. Enter other Network Addresses if
required (003, 004, 005, etc.)
3. FIELD ADJUST MENU If Setpt is other than 160°F (default), enter this menu; otherwise go to
step 4
INTERNAL SETPT
Enter Setpoint temperature
4. CONFIGURATION
MENU
If BLR START LEVEL=20% & BLR STOP LEVEL=16%, skip this menu.
BLR START LEVEL
Enter Boiler Start Level Percent (default = 20%). See Appendix I.
BLR STOP LEVEL
Enter Boiler Stop Level Percent (default = 16%). See Appendix I.