beautypg.com

Appendix h: acs modbus address assignments, Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 127

background image

MC2: 04/23/13 Page 127 of 144

GF-131

AERCO Control System (ACS)

Installation, Operation, and Maintenance Manual

OMM-0081_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

APPENDIX H: ACS MODBUS ADDRESS ASSIGNMENTS

IMPORTANT!

All Modbus addresses specified in this manual are written generically in

hexadecimal format. However, many Building Automation Systems utilize

another form of addressing where:
40001 is added to the generic address for a Holding Register address.
And
30001 is added to the generic address for an Input Register address.
Be sure to check the addressing scheme being used by the BAS that is

being interfaced to the ACS.

H.1 ACS CONTROLLER STANDARD INPUT REGISTER

ASSIGNMENTS

The Read Only Input Register assignments for the ACS are listed in Table H-1 which follows:

Table H-1: ACS Standard Input Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

0 (0x0000)

(Reserved)

1 (0x0001)

Header Temperature

40 to 220°F

2 (0x0002)

Outside Air Temperature

-60 to 120°F

3 (0x0003)

Indoor Air/Return Temperature

40 to 220°F

4 (0x0004)

Fire Rate Out

0 to 100% (out to boilers)

5 (0x0005)

Header Set Temperature

40 to 220°F

6 (0x0006)

Network Address

128 to 247

Default = 128

7 (0x0007)

Total Boilers Fired

0 to 32 (for ACS)

8 (0x0008)

Total Boilers On Line

0 to 32

9 (0x0009)

(Reserved)

10 (0x000A)

Fault/Message Code

0 to 65535

Bit:

0 = Outside Air Sensor

1 = Header Sensor Error

2 = Interlock 1 Error

3 = Interlock 2 Error

4 = Indoor Air Sensor Error/

Return Sensor Error

5 = 4-20mA Input Error

11 (0x000B) thru

15 (0x000F)

(Reserved)

16 (0x0010)

Lead Boiler Number

1 to 32