Table H-2: ACS Standard Holding Register Address Mapping - Continued
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
112 (0x0070) Net Boiler 21
Address
Address for Network Boiler 21
Default = 0
113 (0x0071) Net Boiler 22
Address
Address for Network Boiler 22
Default = 0
114 (0x0072) Net Boiler 23
Address
Address for Network Boiler 23
Default = 0
115 (0x0073) Net Boiler 24
Address
Address for Network Boiler 24
Default = 0
116 (0x0074) Net Boiler 25
Address
Address for Network Boiler 25
Default = 0
117 (0x0075) Net Boiler 26
Address
Address for Network Boiler 26
Default = 0
118 (0x0076) Net Boiler 27
Address
Address for Network Boiler 27
Default = 0
119 (0x0077) Net Boiler 28
Address
Address for Network Boiler 28
Default = 0
120 (0x0078) Net Boiler 29
Address
Address for Network Boiler 29
Default = 0
121 (0x0079) Net Boiler 30
Address
Address for Network Boiler 30
Default = 0
122 (0x007A) Net Boiler 31
Address
Address for Network Boiler 31
Default = 0
**123 (0x007B) Net Boiler 32
Address
Address for Network Boiler 32
Default = 0
124 (0x007C) Network Baud
0=2400, 1=4800, 2=9600, 3=14400,
4=19200
2 = 9600
125 (0x007D) Network Timeout
5 to 240 sec
Default = 60
sec.
126 (0x007E) Password Lo
0 to 255 (73)
Default = 0
127 (0x007F) Password Hi
0 to 255 (79)
Default = 0
128 (0x0080) Modbus Control
Type
0 = Round-Robin
1 = Broadcast
Default = 0
(Round Robin)
129 (0x0081) Modbus Pass-Thru
0 = Disabled
1 = Enabled
Default = 0
(Disabled)
130 (0x0082) RESERVED
Only for BMS II