Chapter 4 Multi-Drop Link Mode Control Procedure
4
■
ID SETUP
■
RS-232C SETUP
Baud rate
Function
Command
Response
Change
WP35n
OK
n = 5: 38400 bps
n = 6: 31250 bps
n = 7: 19200 bps
n = 0: 9600 bps
n = 1: 4800 bps
n = 2: 2400 bps
n = 3: 1200 bps
n = 4: 600 bps
Confirm
RP35
35n
Data length
Change
WP30n
OK
n = 0: 7 bits
n = 1: 8 bits
Confirm
RP30
30n
Parity
Change
WP31n
OK
n = 0: None
n = 1: Set parity
Confirm
RP31
31n
Parity type
Change
WP32n
OK
n = 0: Even
n = 1: Odd
Confirm
RP32
32n
Stop bit length
WP33n
Change
OK
n = 0: 1 bit
n = 1: 2 bits
Confirm
RP33
33n
RTS/CTS
control
Change
WP22n
OK
n = 0: Disable
n = 1: Enable
Confirm
RP322
22n
Registering ID
number (for
each unit)
Function
Command
Response
Description
Change WIDmmn
mm = 01 to 31 (ID 3
number)
n = 0: Do not register
n = 1: Register
mmn
Registering
serial numbers
(Register all ID
numbers more
than the
specified
number.)
Confirm
RIDmm
OK
Change
WIDMAXmm OK
mm = 01 to 31 (ID 4
number)
* If “mm” is “99” in the
response, serial ID
numbers are not
registered.
Confirm
RWIDMAXmm MAXmm
Registering all
serial numbers
Change
WIDAnnn...n OK
n = 0: Do not register
n = 1: Register
* “n” corresponds to ID
numbers (1 to 31) in
ascending order.
Confirm
RIDA
Annn...n
00, 01,
02, 05,
07, 14
00, 01,
02, 05,
14
00, 02,
05, 07,
14
Error code
Error code
00, 02,
05, 08,
14
Description
* To set the parity type,
use the "Parity type"
command.
00, 02,
05, 07,
14