beautypg.com

Modbus-rtu (over rs-485), Modbus setup, Modbus functions – Hardy HI 6500 Series User Manual

Page 51: Modbus registers, Network command interface

background image

Network Configuration 43

Modbus-RTU (over RS-485)

Step 1. Setup a slave address assigned to the HI 6500 series instrument from the

communications menu and the Modbus-RTU submenu.. Use a unique address
between 1 and 247

Step 2. Set the Baud Rate to the same as the master device, typically 9600 or 19,200

Step 3. Set the Parity Bit parameter to match that of the Modbus-RTU master (EVEN,

ODD, or OFF)

The RS 485 half duplex pinout is:

Modbus Setup

Slave Address may be set to any number in the range of 1-247.

Set Baud Rate parameter to match the settings of the Modbus master

Set Parity to match the settings of the Modbus master

Modbus Functions

The Modbus functions allowed in the HI 6500 are:

Function 3: Modbus Read Holding Registers

Function 4: Modbus Read Input Registers

Function 6: Modbus Write Single Register

Function 16 (0x10): Modbus Write Multiple Registers.

Modbus Registers

This instrument has 64 16-bit MODBUS input registers and 64 16-bit output registers. The
data in these registers is in "big endian" format, meaning that the most significant byte
comes first.

The first 6 registers (0 – 5) are used for the “command interface” in the unit.

Registers 6 & 7 will contain the Net weight in 32 bit floating point format.

Registers 8 & 9 will contain the Gross weight in 32 bit floating point format.

Registers 10 and 11 will contain the statusword

Registers 12 and 13 are for the count function.

Network Command Interface

The "network command interface" uses 6 registers (0 – 5) in and 6 registers out.

Register 0: command (shown below)

Register 1: status

Registers 2, 3: Parameter number. See the diagnostics/parameters web page for a list of

parameter numbers.

GND

DNC

TR+

TR-

PrtRX

PrtTX

Signal
Ground

DO Not
Connect

TX+ & Rx- RX+

RS-232 
Pins not

Printer
used