beautypg.com

5 using the xe serial command, Using the xe serial command, E section 11.1.5 on – Rice Lake 720i Programmable Indicator/Controller - Installation Manual User Manual

Page 106

background image

100

720i Installation Manual

11.1.5

Using the XE Serial Command

The XE serial command can be used to remotely query the

720i

for the error conditions shown on the front panel.

The XE command returns a decimal number representing any existing error conditions. For multi-scale
applications, the value returned by the XE command represents all error conditions, if any, present on all
configured scales.

If more than one error condition exists, the number returned is the sum of the values representing the error
conditions (see Table 11-4 on page 100). For example, if both a tare error (TAREERR, 65536) and a truck database
checksum error (ETRUCKERR, 8192) have occurred, the XE command returns the value 73728, representing the
sum of those two error conditions.

Table 11-4. Error Codes Returned on XE Command

Error Code

Value

Description

VIRGERR

1

Virgin error

PARMCHKERR

2

Configuration checksum error

LOADCHKERR

4

Calibration checksum error

PRINTCHKERR

8

Print format checksum error

ENVRAMERR

16

General NVRAM error

ENVCRC1ERR

32

Setpoint NVRAM data error

ENVCRC2ERR

64

ENVCRC3ERR

128

ENVCRC4ERR

256

ENVCRC5ERR

512

ENVCRC6ERR

1024

ENVCRC7ERR

2056

ENVCRC8ERR

4096

ETRUCKERR

8192

Truck database checksum error

GRAVERR

16384

Gravity calibration error

ADPHYSICALERR

32768

A/D physical error

TAREERR

65536

Tare checksum error

STRINGERR

262144

String program error

POWER_FAIL

524288

Power failure

RTCERR

1048576

Real time clock error