5 using the xe serial command, Using the xe serial command, E section 11.1.5 on – Rice Lake 720i Programmable Indicator/Controller - Installation Manual User Manual
Page 106
100
720i Installation Manual
11.1.5
Using the XE Serial Command
The XE serial command can be used to remotely query the
720i
for the error conditions shown on the front panel.
The XE command returns a decimal number representing any existing error conditions. For multi-scale
applications, the value returned by the XE command represents all error conditions, if any, present on all
configured scales.
If more than one error condition exists, the number returned is the sum of the values representing the error
conditions (see Table 11-4 on page 100). For example, if both a tare error (TAREERR, 65536) and a truck database
checksum error (ETRUCKERR, 8192) have occurred, the XE command returns the value 73728, representing the
sum of those two error conditions.
Table 11-4. Error Codes Returned on XE Command
Error Code
Value
Description
VIRGERR
1
Virgin error
PARMCHKERR
2
Configuration checksum error
LOADCHKERR
4
Calibration checksum error
PRINTCHKERR
8
Print format checksum error
ENVRAMERR
16
General NVRAM error
ENVCRC1ERR
32
Setpoint NVRAM data error
ENVCRC2ERR
64
ENVCRC3ERR
128
ENVCRC4ERR
256
ENVCRC5ERR
512
ENVCRC6ERR
1024
ENVCRC7ERR
2056
ENVCRC8ERR
4096
ETRUCKERR
8192
Truck database checksum error
GRAVERR
16384
Gravity calibration error
ADPHYSICALERR
32768
A/D physical error
TAREERR
65536
Tare checksum error
STRINGERR
262144
String program error
POWER_FAIL
524288
Power failure
RTCERR
1048576
Real time clock error