KMC Controls SSS-1000 Series User Manual
Installation guide, Mounting, Connections

SSS-1000 Series
1
Installation Guide
Installation Guide
Differential Pressure Flow Sensors
SSS-1000 Series
Mounting
1. Determine the duct’s flow direction and install
the sensor based on the sensor’s flow arrow
imprint.
NOTE: The sensor must be mounted with the
arrow pointing in the direction of the air
flow.
2. Cut a 7/8" hole in the duct to accept the sensor
probes.
3. Attach using two self-tapping screws inserted in
the 3/16" mounting holes.
Connections
Connections use 3/8" (SSS-100x) or OD polyethylene
tubing. Check that there are no sharp bends in the
tubing at any connection. Bends and creases may
leak as tubing ages.
1. Connect the Port “H” to the “High” input on the
VAV controller.
2. Connect the Port “L” to the “Low” input on the VAV
controller.
NOTE:
For using SSS-100x sensors with CSC-
3000 series, CSP-4000/5000 series,
KMD-7000 series, and BAC-7000 series
controllers, use a 3/8" to 1/4" barb union
adapter and appropriate polyethylene
tubing to the sensor and controller. For
maximum accuracy in the CSP-5000 series,
KMD-7000 series, and BAC-7000 series
controllers, the 3/8" OD tubing between the
sensor and the adapter should be as short as
possible, and the 1/4" OD tubing from the
adapter to the controller should be 24" long
(on both the High and the Low sides). OR
use the equivalent SSS-101x sensor.
Mounting 1
Connections 1
Select Specifications 2
Maintenance 2
More Information 2
Important Notices 2