STE-1415/1416/1417
2
Installation Guide
© 2014 KMC Controls, Inc.
717-019-16D
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
Specifications
Sensor
Type III thermistor, 10K ohm @
77° F (25° C)
Temperature Limits –4 to 221° F (–20 to 105° C)
Wiring
FT6 plenum-rated, 22 AWG
wire leads
Enclosure
Flame-retardant ABS plastic
Cable Lengths and Number of Discrete Sensors
STE-1415
6 feet (1.8 m), 4 sensors
STE-1416
12 feet (3.6 m), 4 sensors
STE-1417
24 feet (7.3 m), 9 sensors
Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long-term reliability
and performance. Careful installation will also
ensure long term reliability and performance.
Connections and Wiring
1. Feed wires from the controller through the
conduit opening.
2. Make connections to the two sensor wire leads
with either butt-splices or solder. (Using wire
nuts is not recommended.) The two-wire sensor is
not polarity sensitive.
3. Plug the conduit with plumber’s putty, painter’s
putty, caulk, or other sealant to prevent air
infiltration.
Configuration
For controller configuration, see
More Information
For additional information,
see the
on the KMC
web site.
For troubleshooting, con-
troller configuration, and
other information, see the
web site.
Important Notices
The KMC logo and KMC Controls are registered
trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may
be reproduced, transmitted, transcribed, stored in a
retrieval system, or translated into any language in
any form by any means without the written permis-
sion of KMC Controls, Inc.
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.