beautypg.com

Set-up, Configuration, Jumper settings – KMC Controls TPE-1464 Series(2008 and later) User Manual

Page 3: Range, Slow damping, Output reverse, Operation, Calibration, Maintenance, Set-up 3

background image

TPE-1464 Series Gauge Pressure Transducers

3

Installation Guide

Set-Up

Configuration

Jumpers and switches are used to select the output

signal type, the input pressure range, and several

options. The device is factory configured to operate

in the 4 to 20 mA output mode but can be changed to

voltage mode by moving the two jumpers from the

CURRENT positions to the VOLTAGE positions.

CAUTION

Change the output jumper positions only while the

power is removed.

Always note the current jumper position before

moving them to the new position. If the jumpers
are rotated 90 degrees and installed incorrectly
the product will not work and damage may occur.

Output Reverse

This switch reverses the output signal polarity. In

reverse mode the analog output is maximum when

the pressure differential is zero and decreases as

pressure increases.

JUMPER SETTINGS

4–20 mA output 0–10 VDC output 0–5 VDC output

Jumper Settings

For voltage/current/range selection, see the illustra-

tion for jumper settings.

Operation

For normal operation such as 0 to 100 psi, the port is

used to measure a positive pressure and 0 psi = 4 mA

or 0 VDC and 100 psi = 20 mA or or 10 VDC (on 10 V

range).

Calibration

With the port open to the ambient pressure or

equalized at 0 pressure:

1. Press and hold the auto-zero button or provide

contact closure between the ZERO and COMMON
terminals for at least 3 seconds.

2. Release the button, and the device will calculate

and store the new zero point.

NOTE: To protect the unit from accidental zeroing

this feature is enabled only when the

detected pressure on both ports is less than

5% of the full range.

© 2014 KMC Controls, Inc.

717-019-03B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliability

and performance. Careful installation will also

ensure long-term reliability and performance.

Range

NOTE: Range and Options switches can be

changed while the unit is operating, but

change the Output jumpers only with the

power removed.

Model

0 to x Pressure Range (Switch Position)

1

2

3

4

1464-1

100 psi

50 psi

20 psi

10 psi

1464-2

200 psi

100 psi

40 psi

20 psi

1464-3

500 psi

250 psi

100 psi

50 psi

Slow Damping

For surge dampening, this switch provides an

averaging period of 8 seconds instead of the default

4 seconds.