CTC-1611/1612

2

Installation Guide

Connections

The CTC-1611/1612 requires an HFO-0028 tubing kit

and a 14.4 scim restrictor T.
1. Insert the restrictor into the HFO-0028 tubing.
2. Connect the restrictor to Port T1.
3. Connect the open side of the T with tubing to the

final device actuator (DA unit for the CTC-1611

or RA unit for the CTC-1612).

Adjustments

© 2012 KMC Controls, Inc.

510-019-01D

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Important Notices

For specifications and accessories, see the

CTC-

1611/1622 Data Sheet

on the KMC web site.

The material in this document is for information pur-

poses only. The contents and the product it describes

are subject to change without notice. KMC Controls,

Inc. makes no representations or warranties with respect

to this document. In no event shall KMC Controls, Inc.

be liable for any damages, direct or incidental, arising

out of or related to the use of this document.

Maintenance

Remove dust as necessary from the slots. Clean the

window with soft, damp cloth and mild soap.
Care should be taken to keep the unit clean

from dust during installation. Each component is

designed for dependable, long-term reliability, and

performance. Careful installation will also ensure

long-term reliability and performance.

6. Replace the gauge tap rubber cap after

calibrating.

7. Place the setpoint slider to the desired

temperature and replace the cover.

Throttling Range

Throttling range is the temperature required to

change the thermostat output pressure from 3–15 psi.

All CTC-1600 series thermostats are factory-set for

a 3° F throttling range. The approximate throttling

range setting is stamped on each lever in both °F and

°C. If it is necessary to change this setting, reverify

calibration after adjustment.
1. Remove scale plate (see the Scale Plate section).
2. Slide the black TR adjuster to appropriate value/

location.

NOTE: The hole in the TR adjuster fits a 1/16" hex

wrench. Gently rotate the adjuster back and

forth while sliding. Do not turn excessively!

3. Rotate back to a “square” position after adjust-

ment.

4. Reinstall the scale plate.

Calibration

These thermostats are factory calibrated and do not

require further calibration at installation. Should it

be necessary to change calibration:
1. Remove the cover and gauge tap rubber cap.
2. Install a gauge on the gauge tap using 3/32" ID

tube.

3. Measure the ambient temperature with an

accurate thermometer.

4. Move the setpoint slider to the measured ambient

temperature.

5. Use a 1/16" hex wrench and turn the calibration

adjustment until the test gauge indicates the

desired pressure. (Clockwise rotation decreases

the output pressure.)