Adjustments and Calibration

Upon receipt, no thermal calibration should be
required.

Flow control points can be calibrated before or after
installation.

1. Verify 9.1 VDC between (+) and (-) terminals.

Refer to wiring diagram.

2. Measure T1 output voltage.

3. Refer to the graphs (right) to make adjustments.

4. Always adjust the minimum flow first.

a. DA Cooling; Set point > Room Temp.
b. RA Heating; Set point < Room Temp.

5. Always adjust maximum limits to a value higher

than the minimum limits. If in doubt, turn Max.
limit fully clockwise (increase) before
proceeding.

a. DA Cooling; Set point < Room Temp.
b. RA Heating; Set point > Room Temp.

Maintenance

No routine maintenance is required. Each
component is designed for dependable, long term
reliability and performance. Careful installation will
also ensure long term reliability and performance.