beautypg.com

Mounting, Specifications – KMC Controls CSC-2000 Series User Manual

Page 2

background image

CSC-2000 Series Reset Volume Controllers

2

Installation Guide

Mounting

As close to the flow sensor pickup as is feasible,

fasten the mounting bracket to the mounting surface

with two self-threading screws in the two 3/16 in.

(5 mm) holes. (Make sure to leave enough room to

make connections.)
The CSC-2000 series are position sensitive:

• The minimum and maximum flow limits must

be set (calibrated) in the same position the

controller will be mounted.

• The CSC-2001/2002 (with 0–10 molded plastic

dials) must be mounted horizontally with dial

adjustment knobs facing up.

• The CSC-2003 through CSC-2018 (no molded

dials) may be mounted horizontally (preferred),

with the adjustment knobs up or down, or

mounted vertically

(the diaphragm inside must

be in a horizontal or vertical plane).

NOTE: If replacing a CSC-2001-22 or CSC-2002-22

(designed for vertical mount and now

obsolete), use the CSC-2001 or CSC-2002 as

appropriate and mount dials face up or use

the CSC-2003 or CSC-2004 as appropriate

and mount vertically or horizontally.

Direct Acting BEIGE units (CSC-2001/2003/2007/

2009/2017) are designed for normally open dampers

with direct-acting thermostats for cooling and re-

verse-acting thermostats for heating.

Reverse Acting GRAY units (CSC-2002/2004/2008/

2010/2018) are designed for normally closed damp-

ers with reverse-acting thermostats for cooling and

direct-acting thermostats for heating.

Specifications

Output Sensitivity

0 to 1" range unit,

5 psig/0.02" wg (35 kPa/5 Pa)

0 to 2" range units,

5 psig/0.04"wg (35 kPa/10 Pa)

Main Air Pressure

15 to 30 psig (103 to 207 kPa)

Max. Signal Pressure 6" wg (1493 Pa) applied to

either port (X or Y)

Material

Flame retardant plastic (beige

or gray)

Output Capability

0 to supply pressure

Weight

7.5 oz. (213 grams)

Temperature Limits
Operating

40° to 120° F (4° to 49° C)

Shipping

–40° to 140° F (–40° to 60° C)

For additional specifications of particular models,

see the CSC-2000 Data Sheet.

With 0–10 Molded Plastic Dial

(CSC-2001/2002)

Without

Molded Dial

(CSC-2003

through CSC-

2018)

Horizontal Mount,

Knobs Up Only

Horizontal Mount

(Preferred, Knobs Up or Down)

Or Vertical Mount