CSC-3000 Series

2

Installation Guide

NOTE: The reverse reset illustration above assumes no

relays between the thermostat and

“T”

port.

For Reverse Reset (RA thermostat for cooling or DA

thermostat for heating), perform the following steps:
1. Disconnect the “T” port and leave it open. Temporarily

plug the open tubing.

2. Adjust the LO STAT ∆P (center dial) to the desired

Maximum airflow.

3. Reconnect the tubing at port “T”.
4. Adjust the thermostat to call for minimum airflow (15

psi or more at “T” port).

5. Adjust the HI STAT ∆P (dial on the right) to the

desired Minimum airflow.

6. Repeat Steps 1 through 5 to verify the settings.

DIRECT Reset Minimum and Maximum

NOTE: The direct reset illustration above assumes no

relays between the thermostat and

“T”

port.

For Direct Reset (DA thermostat for cooling or RA

thermostat for heating), perform the following steps:
1. Disconnect the “T” port. Temporarily plug the tubing.

(Do NOT plug the port.)

2. Adjust the LO STAT ∆P (center dial) to the desired

Minimum airflow.

3. Reconnect the tubing at “T” port.
4. Adjust thermostat to call for full airflow (15 psi or

more at “T” port).

5. Adjust the HI STAT ∆P (dial on right) to the desired

Maximum airflow.

6. Repeat Steps 1 through 5 to verify the settings.

More Information

For specifications, see the Data Sheet for

these controllers. For additional adjust-

ments, calibration, troubleshooting,

principles of operation, and sample ap-

plications, see the

Application Guide

for

these controllers. For support documents,

see the CSC-3000 series

product page (bit.ly/y0G2sI)

on

the

KMC Controls web site (kmccontrols.com)

.

This Installation Guide does not apply to the CSC-3014

(designed to work with CTC-2100 Thermostats) or the

CSC-3501/3505 (Linear Volume Reset Controllers). See

their separate Data Sheets and Installation Guides.

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Important Notices

The material in this document is for information purposes

only. The contents and the product it describes are subject to

change without notice. KMC Controls, Inc. makes no represen-

tations or warranties with respect to this document. In no event

shall KMC Controls, Inc. be liable for any damages, direct or

incidental, arising out of or related to the use of this document.

© 2012 KMC Controls, Inc.

213-019-01M

REVERSE Reset Minimum and Maximum

Adjustments and Calibration

NOTE: Do NOT adjust start point and span (upper and

lower knobs) without thoroughly reviewing the

Application Guide. For information about direct

vs. reverse reset, see the Application Guide.

Damper Action

The damper action is factory-set at Normally Open (NO).

To change to Normally Closed (NC):
1. Loosen the damper selection screw.
2. Turn the selection dial clockwise until the “NC” arrow

aligns with the “DAMPER” arrow.

NOTE: Accuracy in the alignment of the arrows is

very important. Make this adjustment as exact

as possible.

3. Tighten the selection screw. Be sure the screw is tight

(2 to 4 in-lbs. of torque), but if overtightened, the

plastic will strip out.

Adjusting Minimums and Maximums

When adjusting the minimum and maximum flow

settings, the output responds slowly to changes in the

setpoint. Wait for the flow rate to stabilize after making

an adjustment (usually 20 to 30 seconds) before making

further adjustments. Also, if the damper position is all

the way closed or open when starting this step, turn the

adjustment one full turn, and then wait 20 to 30 seconds

for a change in the flow reading of the Magnehelic gauge.

If no change occurs after this time, repeat until the flow

rate changes. (See the Application Guide for more tips.)

Thermostat Pressure

Max. Airflow

Min. Airflow

Reset Start Point
• 3 psig: CSC-3021/3026
• 8 psig: CSC-3011/3016/3017/3025
• 10 psig: CSC-3023

Reset Span (5 psig)

(Cooling w/ DA Thermstat or

Heating w/ RA Thermostat)

Thermostat Pressure

Max. Airflow

Min. Airflow

Reset Start Point
• 3 psig: CSC-3021/3026
• 8 psig: CSC-3011/3016/3017/3025
• 10 psig: CSC-3023

Reset Span (5 psig)

(Cooling w/ RA Thermstat or

Heating w/ DA Thermostat)