Toolbox Menu (1 of 2)

Item Field

Range

Description

Error Display

Access: ---

ERROR

If an error is present, it will be displayed as the first item in the toolbox menu.
Additional troubleshooting information scrolls on the display. For more information
about error messages, refer to the Error Messages section of this document.

USER, INST, ADV

Default: INST

Access: USER

ACCESS LEVEL

The access level of the control. The access column shows which items are visible
in each access level.
This item is only available if the Lock / Unlock switch is set to Unlock.

OFF, SEL, DONE

Default: OFF

Access: ADV

DEFAULT

Press the Enter button to show SEL. After 3 seconds DONE will be indicated &
factory defaults will be loaded to all settings.

284, Software Version

Access: USER

TYPE & SOFTWARE VERSION

Product number of the control displayed in the number field. Software version
displayed in the item field.

°F or °C

Default: °F

Access: USER

TEMPERATURE UNITS

Units for display of temperature.

gpm or m³/h

Default: gpm

Access: INST

FLOW RATE UNITS

Units for display of flow rate.
This item is only available if Flow Sensor is set to ON.

MBtu or kWh

Default: MBtu

Access: INST

ENERGY UNITS

Units for display of Energy. If MBtu is selected, the units used for Energy are Therms
(THRM). If kWh is selected, the units used for Energy are Gigajoules (GJ).
This item is only available if Flow Sensor is set to ON.

psi or kPa

Default: psi

Access: INST

PRESSURE UNITS

Units for display of pressure.
This item is only available if Pressure Sensor is set to ON.

1 to 24

Access: INST

BOILER BUS B DEVICES

Displays the number of tN4 devices connected to the Boiler Bus b terminals, tN4
& C0 (32 & 33).

1 to 24

Access: INST

BOILER BUS 1 DEVICES

Displays the number of tN4 devices connected to the Boiler Bus 1 terminals, tN4
& C1 (34 & 35).

1 to 24

Access: INST

BOILER BUS 2 DEVICES

Displays the number of tN4 devices connected to the Boiler Bus 2 terminals, tN4
& C2 (36 & 37).