Testing the sensor wiring, Wiring the tekmarnet, Devices tn4 boiler bus b – tekmar 284 Boiler Control User Manual

Page 30: Tn4 boiler bus 1, Tn4 boiler bus 2, Tn4 boiler bus 3

background image

© 2014

284_D - 08/14

30 of 60

A Watts Water Technologies Company

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

°F

°C

°F

°C

°F

°C

°F

°C

-50

-46

490,813

20

-7

46,218

90

32

7,334

160

71

1,689

-45

-43

405,710

25

-4

39,913

95

35

6,532

165

74

1,538

-40

-40

336,606

30

-1

34,558

100

38

5,828

170

77

1,403

-35

-37

280,279

35

2

29,996

105

41

5,210

175

79

1,281

-30

-34

234,196

40

4

26,099

110

43

4,665

180

82

1,172

-25

-32

196,358

45

7

22,763

115

46

4,184

185

85

1,073

-20

-29

165,180

50

10

19,900

120

49

3,760

190

88

983

-15

-26

139,403

55

13

17,436

125

52

3,383

195

91

903

-10

-23

118,018

60

16

15,311

130

54

3,050

200

93

829

-5

-21

100,221

65

18

13,474

135

57

2,754

205

96

763

0

-18

85,362

70

21

11,883

140

60

2,490

210

99

703

5

-15

72,918

75

24

10,501

145

63

2,255

215

102

648

10

-12

62,465

80

27

9,299

150

66

2,045

220

104

598

15

-9

53,658

85

29

8,250

155

68

1,857

225

107

553

Testing the Sensor Wiring

A good quality test meter capable of measuring up to 5,000 kΩ
(1 kΩ = 1000 Ω) is required to measure the sensor resistance. In
addition to this, the actual temperature must be measured with
either a good quality digital thermometer, or if a thermometer
is not available, a second sensor can be placed alongside the
one to be tested & the readings compared.
First measure the temperature using the thermometer & then
measure the resistance of the sensor at the control. The wires
from the sensor must not be connected to the control while the
test is performed. Using the chart below, estimate the temperature

measured by the sensor. The sensor & thermometer readings
should be close. If the test meter reads a very high resistance,
there may be a broken wire, a poor wiring connection or a
defective sensor. If the resistance is very low, the wiring may
be shorted, there may be moisture in the sensor or the sensor
may be defective. To test for a defective sensor, measure the
resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage
to the sensor may result.

Wiring the tekmarNet

®

Devices

tN4 Boiler Bus b

Terminals 32 - 33

Terminals 32 & 33 provide communication for tN4 devices on the tN4 Boiler Bus b. Connect terminals 32 (tN4) & 33 (C0) to the
corresponding terminals on the tN4 devices that are to be connected.
The connection is polarity sensitive. Ensure that terminal 32 (tN4) is connected to the tN4 terminal on the tN4 device &
that terminal 33 (C0) is connected to the C terminal on the tN4 device.

tN4 Boiler Bus 1

Terminals 34 - 35

Terminals 34 & 35 provide communication for tN4 devices on the tN4 Boiler Bus 1. Connect terminals 34 (tN4) & 35 (C1) to the
corresponding terminals on the tN4 devices that are to be connected.
The connection is polarity sensitive. Ensure that terminal 34 (tN4) is connected to the tN4 terminal on the tN4 device &
that terminal 35 (C1) is connected to the C terminal on the tN4 device.

tN4 Boiler Bus 2

Terminals 36 - 37

Terminals 36 & 37 provide communication for tN4 devices on the tN4 Boiler Bus 2. Connect terminals 36 (tN4) & 37 (C2) to the
corresponding terminals on the tN4 devices that are to be connected.
The connection is polarity sensitive. Ensure that terminal 36 (tN4) is connected to the tN4 terminal on the tN4 device &
that terminal 37 (C2) is connected to the C terminal on the tN4 device.

tN4 Boiler Bus 3

Terminals 38 - 39

Terminals 38 & 39 provide communication for tN4 devices on the tN4 Boiler Bus 3. Connect terminals 38 (tN4) & 39 (C3) to the
corresponding terminals on the tN4 devices that are to be connected.
The connection is polarity sensitive. Ensure that terminal 38 (tN4) is connected to the tN4 terminal on the tN4 device &
that terminal 39 (C3) is connected to the C terminal on the tN4 device.