Navigating The Display

The menu items of the 284 are described in detail in the following pages. The number of available items changes depending on
the control configuration. To find out what other settings affect the display of an item, refer to the menu descriptions.

View Menu

(default display)

Press

& hold

Navigate
available

menus

Setup
Source 1
Source 2
Source 3
Source 4
Monitor
Monitor 1
Monitor 2
Monitor 3
Monitor 4
Schedule
Time
BAS
Toolbox

Enter

selected

menu

Change

item

setting

Navigate
available

items

Press

once

Press

twice

View Menu (1 of 2)

Item Field

Range

Description

Access: User

TIME

Current date & time.
This item is only available when the Setback / Off switch is set to Setback & Clock
(Time menu) is set to ON.

---, -76 to 149°F

(-60.0 to 65.0°C)

Access: User

OUTDOOR

Current outdoor temperature as measured by the outdoor sensor. “----” is displayed
if there is a sensor fault.
This item is only available when Application Mode is set to RSET or an outdoor
sensor is connected.

---, -22 to 266°F

(-30 to 130°C)

Access: User

BOILER SUPPLY

Current boiler supply water temperature as measured by the boiler supply sensor.
“----” is displayed if there is a sensor fault.

---, -22 to 266°F

(-30 to 130°C)

Access: ADV

BOILER TARGET

The boiler target is the temperature the control is trying to maintain at the boiler supply
sensor. “----” is displayed when no heat is required.

---, -22 to 266°F

(-30.0 to 130.0°C)

Access: ADV

INDIRECT DHW EXCHANGE TEMPERATURE

The indirect DHW exchange target is the temperature the control is trying to
maintain at the boiler 4 outlet sensor. “----” is displayed when no heat is required.
This item is only available if Application Mode is set to RSET, SETP or EMS, IDHW
Mode is set to ON & IDHW Location is set to NEAR.

---, -22 to 266°F

(-30.0 to 130.0°C)

Access: User

INDIRECT DHW

Current indirect DHW tank temperature as measured by the DHW sensor. “----” is
displayed if there is a sensor fault.
This item is only available if Application Mode is set to RSET, SETP or EMS, IDHW
Mode is set to ON & IDHW Sensor is set to ON.

The View Menu includes general information about boiler & pump operation, calls & temperatures. The View Menu is the default
display of the 284.