Control settings – tekmar 284 Boiler Control User Manual
Page 33

© 2014
284_D - 08/14
33 of 60
A Watts Water Technologies Company
Access Level
DIP
Description
Default
Lock / Unlock & Access Levels
Use this DIP switch to lock & unlock the Access Level of the 284 & all connected
tN4 devices, including tN4 thermostats. For details, see above.
Once unlocked, the access level can be changed in the Toolbox menu.
Once locked, the access level in all devices cannot be viewed or
changed.
When the control is locked a small segment representing a padlock is show
in the display.
•
•
•
Unlocked
External Flow Proof / Off
External Flow Proof / Off
Use this DIP switch to select whether or not the Flow Proof Feature is to be
used.
If the Flow Proof feature is being used, set the DIP switch to the External
Flow Proof position. The control must receive an external Flow Proof Call
within a period of time once a primary pump is turned on.
If the Flow Proof feature is not being used, set the DIP switch to the Off
position.
The flow proof call feature can only be used when the control is
configured to operate the primary pump for all loads. If there are
multiple loads (e.g. Heat Call and DHW Call) and the primary pump
is disabled for DHW operation, then the control cannot provide flow
proving and the feature must be disabled. In this case, the flow proof
feature must be obtained through another control such as the Pump
Sequencer 132.
•
•
•
Off
External C.A. Proof / Off
External C.A. Proof / Off
Use this DIP switch to select whether or not the C.A. Proof Feature is to be
used.
If the C.A. Proof feature is being used, set the DIP switch to the External
C.A. Proof position. The control must receive an external C.A Proof Call
within a period of time once the C.A. damper is turned on.
If the C.A. Proof feature is not being used, set the DIP switch to the Off
position.
•
•
Off
Off / Exercise
Off / Exercise
Use this DIP switch to select whether or not the control is to exercise all pumps
for 10 seconds every three days of inactivity.
Exercise
Setback / Off
Setback / Off
Use this DIP switch to select whether or not the control is to follow a
schedule.
Off
The access level restricts the number of menus & items that
can be accessed by the user. The Access Level setting is
found in the Toolbox menu. Select the appropriate access
level for the people who work with the control on a regular
basis. There are three Access Level settings:
User (USER): Select this access level to limit the number
of items available to the end user.
Installer (INST): Select this access level to limit some of the
•
•
items available to the installer. This is the factory default
access level. The 284 defaults to the ‘Installer’ access
level after 24 hours.
Advanced (ADV): Select this access level to have complete
access to all of the items.
The Lock / Unlock switch on the front of the control must
be set the Unlock position to change the access level.
•
DIP Switch Settings
Control Settings