tekmar 284 Boiler Control User Manual

Page 41

background image

© 2014

284_D - 08/14

41 of 60

A Watts Water Technologies Company

Setup Menu (5 of 6)

Item Field

Range

Description

OFF or ON

Default: OFF

Access: ADV

INDIRECT DHW PRIORITY

Selects whether indirect DHW priority is active or not.
This item is only available when Application Mode is set to RSET or EMS & Indirect
DHW Mode is set to ON.

1 to 4

Default: 2

Access: ADV

INDIRECT DHW BOILER COUNT

Selects the number of boilers to be used when only a DHW Call is present.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Indirect DHW Mode is set to ON & Indirect DHW Location is set to Boil.

OFF or ON

Default: OFF

Access: ADV

PRIMARY PUMP DURING IDHW OPERATION

Selects whether or not the primary pump is required to operate when a DHW
Call is present.
This item is only available when APP MODE is set to RSET, SETP or EMS, Primary
Pump 1 or Primary Pump 2 is set to AUTO, Indirect DHW Mode is set to ON &
Indirect DHW Location is set to Boil.

OFF or ON

Default: OFF

Access: ADV

SETPOINT MODE

Selects whether setpoint operation is active or not.
This item is only available when Application Mode is set to RSET, SETP or
EMS.

OFF or ON

Default: OFF

Access: ADV

SETPOINT PRIORITY

Selects whether setpoint priority is active or not.
This item is only available when Application Mode is set to RSET or EMS &
Setpoint Mode is set to ON.

OFF or ON

Default: OFF

Access: ADV

PRIMARY PUMP DURING SETPOINT OPERATION

Selects whether or not the primary pump is required to operate when a Setpoint
Call is present.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Primary Pump 1 or Primary Pump 2 is set to AUTO & Setpoint Mode is set to
ON.

60 to 220°F

(15.5 to 104.0°C)

Default: 180°F (82.0°C)

Access: ADV

SETPOINT OCCUPIED TEMPERATURE

The boiler target temperature when a Setpoint Call is present during the occupied
periods.
This item is only available when Application Mode is set to RSET, SETP or EMS
& Setpoint Mode is set to ON.

OFF, 60 to 220°F

(15.5 to 104.0°C)

Default: OFF

Access: ADV

SETPOINT UNOCCUPIED TEMPERATURE

The boiler target temperature when a Setpoint Call is present during the unoccupied
periods. If operation is not desired during the unoccupied periods, select OFF.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Setpoint Mode is set to ON & the Setback / Off switch is set to Setback

70 to 190°F

(21.0 to 88.0°C)

Default: 140°F (60.0°C)

Access: ADV

DEDICATED DHW OCCUPIED SETPOINT

The temperature of the dedicated DHW tank during the occupied periods.
This item is only available when Application Mode is set to DDHW.

OFF, 70 to 190°F

(21.0 to 88.0°C)

Default: OFF

Access: ADV

DEDICATED DHW UNOCCUPIED SETPOINT

The temperature of the dedicated DHW tank during the unoccupied periods.
This item is only available when Application Mode is set to DDHW & the Setback
/ Off switch is set to Setback.