tekmar 256 Boiler Control User Manual

Installation & operation manual, D 256, Boiler control 256

background image

The Boiler Control 256 is designed to control a single stage heat source in order to provide outdoor reset. The control has a Liquid
Crystal Display (LCD) to view system status and operating information.

• Test sequence to ensure proper boiler operation

• Setback input for energy savings

• CSA C US certifi ed (approved to applicable UL standards)

Additional functions include:

• Quick Setup for easy installation and programming of control

• User comfort adjustment to increase or decrease building space

temperature

• Advanced settings to fi ne-tune building requirements

- Installation & Operation Manual

Boiler Control 256

D 256

07/11

1 of 20

© 2011

D 256 - 07/11

Input

Outdoor Sensor

Included

Input

Universal Sensor

Included

Input

24 V (ac)

Power Supply

Output

Boiler

Input

tekmar Timer

Optional

BOIL

F

OCC

Input

Boiler Demand

Signal

PRGM

S

T I M E

AMPM

UNOCC

OVR

S

M

W T F

T

1
2

Press & Release:
all 3 buttons, to adjust menu

Press & Hold:
Item, to view settings
, to test.

Boiler Control 256

One Stage Boiler

Item

Dat

e Code

Power: 24 V ±10% 50/60 Hz

3 VA Class 2

Relay:

240 V (ac) 5 A 1/6 hp

Meets Class B:
Canadian ICES
FCC Part 15

H1

190D

Terminal Unit

Boiler Demand

Ins

t / A

dv

1

Boil

2

Out

3

Com

4

UnO

Sw

5

Boiler

6

7

T

8

Power

R+

9

C-

Do not apply power

tektra 909-01

Designed &

Assembled in

Canada

Signal wiring

must be rated

at least 300V

Note:
Boiler demand must have
an electrical closure
between terminals 7
and 9 before the boiler
is able to fire.