tekmar 070 Outdoor Sensor User Manual
Installation & operation manual, 070_d, Outdoor sensor 070
Outdoor Sensor 070
Installation & Operation Manual
070_D
12/12
Accessories Replaces: 05/07
© 2012
070_D - 12/12
1 of 4
A Watts Water Technologies Company
The Outdoor Sensor 070 provides accurate measurement of the outdoor air temperature.
Many controls and thermostats can connect to the 070 to measure and display the
outdoor temperature.
STEP ONE
MOUNTING THE SENSOR
NOTE: The temperature sensor (thermistor) is built into the 070 enclosure.
• Remove the screw and pull the front cover off the sensor enclosure.
• The 070 can either be mounted directly onto a wall or a 2” x 4” electrical box. When
the 070 is wall mounted, the wiring should enter through the back or bottom of the
enclosure. Do not mount the 070 with the conduit knockout facing upwards as rain
could enter the enclosure and damage the sensor.
• In order to prevent heat transmitted through the wall from affecting the sensor read-
ing, it may be necessary to install an insulating barrier behind the enclosure.
• The 070 should be mounted on a wall which best represents the heat load on the
building (a northern wall for most buildings and a southern facing wall for buildings
with large south facing glass areas). The 070 should not be exposed to heat sources
such as ventilation or window openings.
• The 070 should be installed at an elevation above the ground that will prevent
accidental damage or tampering.
Sensor with bottom
entry wiring
Sensor with rear
entry wiring
Sensor mounted
onto 2" x 4"
electrical box
Installation - Outdoor Sensor 070