tekmar 284 Boiler Control User Manual

Page 42

background image

© 2014

284_D - 08/14

42 of 60

A Watts Water Technologies Company

Setup Menu (6 of 6)

Item Field

Range

Description

2 to 10°F

(1.0 to 5.5°C)

Default: 5°F (3.0°C)

Access: ADV

DEDICATED DHW DIFFERENTIAL

The temperature differential of the dedicated DHW tank from the DDHW SETPOINT
settings.
This item is only available when Application Mode is set to DDHW.

OFF, AUTO, 0:20 to

4:00 hrs

Default: OFF

Access: ADV

PRIORITY OVERRIDE

The amount of time priority is given for indirect DHW or setpoint operation before
space heating resumes.
This item is only available when Application Mode is set to RSET or EMS, &
Indirect DHW Mode is set to ON & Indirect DHW Priority is set to ON, or Setpoint
Mode is set to ON & Setpoint Priority is set to ON.

35 to 100°F, OFF

(2.0 to 38.0°C)

Default: 70°F (21.0°C)

Access: ADV

WWSD OCCUPIED

The system’s warm weather shutdown temperature during the occupied
periods.
This item is only available when the Application Mode is set to RSET.

35 to 100°F, OFF

(2.0 to 38.0°C)

Default:

60°F (15.5°C)

Access: ADV

WWSD UNOCCUPIED

The system’s warm weather shutdown temperature during the unoccupied
periods.
This item is only available when the Application Mode is set to RSET & the Setback
/ Off switch is set to Setback.

OFF, 3 to 40 min

Default: 20 min

Access: ADV

BOILER ALERT

Alert signal if the boiler supply temperature does not increase in temperature, after
all available boilers have been turned on, within the selected time.

OFF or ON

Default: OFF

Access: ADV

FLOW SENSOR

Selects whether or not a flow sensor is used.

0 to 100 gpm

Default: 0 gpm

Access: ADV

FLOW RATE 4MA

Sets the flow rate that corresponds to 4 mA for the flow sensor.
This item is only available when Flow Sensor is set to ON.

100 to 2,000 gpm

Default: 500 gpm

Access: ADV

FLOW RATE 20MA

Sets the flow rate that corresponds to 20 mA for the flow sensor.
This item is only available when Flow Sensor is set to ON.

OFF, 1 to 100%

Default: OFF

Access: ADV

FLOW SENSOR PROOF

Sets the percentage of flow used for proving primary pump flow. If the flow sensor
is only used for monitoring, set to OFF. This is the minimum flow required to prove
primary pump flow.
This item is only available when Flow Sensor is set to ON.

OFF or ON

Default: OFF

Access: ADV

PRESSURE SENSOR

Selects whether or not a pressure sensor is used.

50, 100, 150, 200, 250,

300

Default: 50

Access: ADV

PRESSURE SENSOR RANGE

Selects the model of pressure sensor based on the pressure range in units of
PSI.
This item is only available when Pressure Sensor is set to ON.