Setup Menu (4 of 6)

Item Field

Range

Description

OFF or ON

Default: OFF

Access: ADV

FIXED LAST

Selects whether or not the last boiler is to be excluded from the rotation sequence.
If set to ON, boiler 4 is always the last to fire.
This item is only available if boiler 4 is enabled (Boiler Enable = AUTO) & all
available boilers are either condensing or non-condensing.

AUTO, 5 to 30 min

Default: AUTO

Access: ADV

HEATING CYCLES

The cycle length to which all tN4 devices will synchronize.
This item is only available when Application Mode is set to RSET & a tN4 device
is present.

OFF or ON

Default: OFF

Access: ADV

INDIRECT DHW MODE

Selects whether indirect DHW heating is active or not.
This item is only available when Application Mode is set to RSET, SETP or
EMS.

NEAR or Boil

Default: Boil

Access: ADV

INDIRECT DHW LOCATION

Selects the location of the indirect DHW tank.
NEAR = Near boiler piping supplied by boiler 4.
Boil = Boiler system piping supplied by boiler plant.
This item is only available when Application Mode is set to RSET, SETP or EMS
& Indirect DHW Mode is set to ON. NEAR is only available when Plant Flow is
set to PUMP.

OFF or ON

Default: OFF

Access: ADV

INDIRECT DHW SENSOR

Selects if a DHW Sensor is to be used for indirect DHW heating.
This item is only available when Application Mode is set to RSET, SETP or EMS
& Indirect DHW Mode is set to ON.

70 to 190°F

(21.0 to 88.0°C)

Default: 140°F (60.0°C)

Access: ADV

INDIRECT DHW SETPOINT OCCUPIED

The temperature of the indirect DHW tank during the occupied periods.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Indirect DHW Mode is set to ON & Indirect DHW Sensor is set to ON.

OFF, 70 to 190°F

(21.0 to 88.0°C)

Default: OFF

Access: ADV

INDIRECT DHW SETPOINT UNOCCUPIED

The temperature of the indirect DHW tank during the unoccupied periods. If
operation is not desired during the unoccupied periods, select OFF.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Indirect DHW Mode is set to ON, Indirect DHW Sensor is set to ON & the Setback
/ Off switch is set to Setback.

1 to 42°F

(0.5 to 23.5°C)

Default: 6°F (3.0°C)

Access: ADV

INDIRECT DHW DIFFERENTIAL

The temperature differential of the indirect DHW tank from the IDHW SETPOINT
settings.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Indirect DHW Mode is set to ON & Indirect DHW Sensor is set to ON.

100 to 220°F

(38.0 to 104.0°C)

Default: 180°F (82.0°C)

Access: ADV

INDIRECT DHW EXCHANGE OCCUPIED

The boiler target temperature for the indirect DHW heat exchanger during the
occupied periods.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Indirect DHW Mode is set to ON & Indirect DHW Sensor is set to OFF.

OFF, 100 to 220°F

(OFF, 38.0 to 104.0°C)

Default: OFF

Access: ADV

INDIRECT DHW EXCHANGE UNOCCUPIED

The boiler target temperature for the indirect DHW heat exchanger during the
unoccupied periods. If operation is not desired during the unoccupied periods,
select OFF.
This item is only available when Application Mode is set to RSET, SETP or EMS,
Indirect DHW Mode is set to ON, Indirect DHW Sensor is set to OFF & the Setback
/ Off switch is set to Setback.