Wiring a Heat Call

Terminals 5, 6

Wiring an Indirect DHW (IDHW) Call

Terminals 7, 8

Wiring a Setpoint Call

Terminals 9, 10

The 284 requires a switched external heat call to operate the boiler plant unless calls for heat are generated through
a tekmarNet

®

device, EMS, BACnet

®

or Modbus

®

connection. The heat call can be volt free or up to 24 V (ac).

Connect the Heat Call terminals 5 & 6 to a switched heat demand.
Typical heat calls are from a zone relay box or thermostat.
A permanent heat call can be created by installing a jumper wire between terminals 5 & 6.



If the DHW sensor option is not used, a call for indirect domestic hot water can come from an aquastat connected
to terminals 7 & 8. The IDHW Call can be volt free or up to 24 V (ac).

Connect the IDHW Call terminals 7 & 8 to the DHW tank aquastat.

The Setpoint Call terminals 9 & 10 can receive a call for heat from a setpoint control or thermostat. The setpoint
call can be volt free or up to 24 V (ac).

Connect the Setpoint Call terminals 9 & 10 to the output terminals on a setpoint control or thermostat.

51 52

Mod

Boiler 1

53 54

Stage 1

Stage 2

55

56

+

-

Single Stage Boiler Wiring

Terminals 53 to 72

A single stage condensing or non-condensing boiler is enabled through the T T contacts.

For Boiler 1 connect Stage 1 terminals 53 & 54 to the boiler TT contacts.
For Boiler 2 connect Stage 1 terminals 59 & 60 to the boiler TT contacts.
For Boiler 3 connect Stage 1 terminals 65 & 66 to the boiler TT contacts.
For Boiler 4 connect Stage 1 terminals 71 & 72 to the boiler TT contacts.




Stage 1

T

T

Stage 2

T

T

Stage 1

T

T

51 52

Mod

Boiler 1

53 54

Stage 1

Stage 2

55

56

+

-

Two Stage Boiler Wiring

Terminals 53 to 74

A two stage condensing or non-condensing boiler requires two wires for each stage.

For Boiler 1 connect Stage 1 terminals 53 / 54 & 55 / 56 to the boiler stage 1 & stage 2 contacts.
For Boiler 2 connect Stage 1 terminals 59 / 60 & 61 / 62 to the boiler stage 1 & stage 2 contacts.
For Boiler 3 connect Stage 1 terminals 65 / 66 & 67 / 68 to the boiler stage 1 & stage 2 contacts.
For Boiler 4 connect Stage 1 terminals 71 / 72 & 73 / 74 to the boiler stage 1 & stage 2 contacts.