tekmar 261 Boiler Control User Manual

Data brochure, D 261, Boiler control 261

background image

Copyright © D 261 -

03/09

1 of 20

- Data Brochure

Boiler Control 261

D 261

0

3/09

The Boiler Control 261 is designed to control two separate on / off boiler stages (or one low / high fire) in order to provide outdoor reset
or setpoint operation. The control includes a Liquid Crystal Display (LCD) to view system status and operating information.

Additional functions include:
• Quick Setup for simple installation and programming of control

• User comfort adjustment to increase or decrease building space

temperature

• Advanced settings to fine-tune building requirements

• Powered boiler pump output

• Test sequence to ensure proper component operation

• Setback input for energy savings

• 120 V (ac) power supply

• CSA C US certified (approved to applicable UL standards)

Output

Boiler

Input

Outdoor

Sensor

Included

Output

Boiler System

Pump

Input

120 V (ac) Power

Supply

Input

Boiler Demand

Signal

Input

Universal

Sensor

Included

PRGM

S

T I M E

AMPM

UNOCC

OVR

S

M

W T F

T

1
2

Input

tekmar Timer

Optional

To increase or decrease the

building temperature:

Boiler Control 261

Two Stage Boiler & Setpoint

Terminal Unit

Boiler Demand

C US

158033

Return

Made in Canada by

tekmar Control Systems Ltd.
tektra 910-02

Power:

Relays:

Demand:

120 V

240 V (ac) 10 A 1/3 hp

20 to 260 V (ac) 2 VA

Signal wiring must be

rated at least 300V.

H1

108D

Test

13 14 15 16 17

Do not apply power

UnO

Sw

Com Boil Out Com

11 12

Stage

1

2

3

4

5

6

7

8

Boiler

Demand

L

Power

N

Boil

Pmp N

Setpoint

Demand

Display defaults back to VIEW

menu after 20 sec.

Setpoint

ROOM - Set to desired room temp.

OUTDR DSGN - Set to coldest (design)

outdoor temp.

Installer Instructions

Terminal Unit Set to

High Mass Radiant

Low Mass Radiant

Fan Coil

Convector

Radiator

Baseboard

1

2

3

4

5

6

Setpoint - Set to desired setpoint temp.

Refer to brochure for more information

9 10

Stage

1

1

2

2

Fire Delay

Setpoint Demand

Press the Item, , buttons

simultaneously for 1 sec. to

enter the ADJUST menu

Use the , buttons to

adjust the ROOM setting

Input

Setpoint Demand

Signal

Output

Boiler

Item

BOIL

°F

1 2

OCC

VIEW

Off

Installer

Advanced

Rotate

Meets Class B:

Canadian ICES

FCC Part 15

50/60 Hz 1300 VA

Dat

e Code


Note:
Boiler or setpoint demand
must be powered with 20
to 260 V (ac) before the
boiler is able to fire.