tekmar 284 Boiler Control User Manual

Page 39

background image

© 2014

284_D - 08/14

39 of 60

A Watts Water Technologies Company

Setup Menu (3 of 6)

Item Field

Range

Description

OFF, 0:10 to 3:00 min

Default: 1:00 min

Access: ADV

CA DELAY

The time delay for the first boiler to operate once the C.A. damper (Aux) relay
turns on.
This item is only available if the External C.A. Proof / Off switch is set to Off &
Auxiliary Relay is set to DMPR.

150 to 350°F, OFF

(65.5 to 177.0°C)

Default: OFF

Access: ADV

VENT MAXIMUM

The maximum vent temperature that is used for vent temperature limiting. The
boiler plant will be shut down if the vent temperature rises to the vent maximum
temperature. Set to OFF if only vent temperature monitoring is desired.

AUTO, 0:30 to 40:00

min

Default: AUTO

Access: ADV

STAGE DELAY

The minimum time delay between the operation of boiler stages, either within a
boiler or between boilers.
This item is only available if there are at least two boilers set to auto
(Boiler Enable = AUTO).

SEQ or PAR

Default: PAR

Access: ADV

MODULATION MODE CONDENSING

Selects either sequential or parallel modulation for multiple modulating condensing
boilers.
This item is only available if there are at least two boilers set to auto (ENABLE=AUTO),
condensing (Boiler Condense = YES) & Modulating (Boiler Type = MOD or
EMS).

SEQ, PAR

Default: SEQ

Access: ADV

MODULATION MODE NON-CONDENSING

Selects either sequential or parallel modulation for multiple modulating non-
condensing boilers.
This item is only available if there are at least two boilers set to auto (Boiler Enable
= AUTO), non-condensing (Boiler Condense = NO) & Modulating (Boiler Type =
MOD or EMS).

LHLH or LLHH

Default: LHLH

Access: ADV

STAGING MODE CONDENSING

Selects either low-high-low-high (LHLH) or low-low-high-high (LLHH) staging for
multiple two-stage condensing boilers.
This item is only available if there are at least two boilers set to auto (Boiler
Enable = AUTO), condensing (Boiler Condense = YES) & two stage (Boiler Type
= 2STG).

LHLH or LLHH

Default: LHLH

Access: ADV

STAGING MODE NON-CONDENSING

Selects either low-high-low-high (LHLH) or low-low-high-high (LLHH) staging for
multiple two-stage non-condensing boilers.
This item is only available if there are at least two boilers set to auto (Boiler
Enable = AUTO), non-condensing (Boiler Condense=NO) & two stage (Boiler
Type = 2STG).

OFF or ON

Default: ON

Access: ADV

ROTATION CONDENSING BOILER GROUP

Selects the equal run time rotation feature within the condensing boiler group.
This item is only available if there are at least two boilers set to auto
(Boiler Enable = AUTO) & condensing (Boiler Condense = YES).

OFF or ON

Default: ON

Access: ADV

ROTATION NON-CONDENSING BOILER GROUP

Selects the equal run time rotation feature within the non-condensing boiler
group.
This item is only available if there are at least two boilers set to auto
(Boiler Enable = AUTO) & non-condensing (Boiler Condense = NO).

OFF or ON

Default: OFF

Access: ADV

FIXED LEAD

Selects whether or not the first boiler is to be excluded from the rotation sequence.
If set to ON, boiler 1 is always the first to fire.
This item is only available if boiler 1 is enabled (Boiler Enable = AUTO) & all
available boilers are either condensing or non-condensing.