Setup Menu (2 of 6)

Item Field

Range

Description

OFF, 60 to 180°F

(OFF, 15.5 to 82.0°C)

Default: 140°F (60.0°C)

Access: ADV

BOILER MINIMUM

The minimum allowed boiler target temperature used for the non-condensing
boiler group. Check the boiler manufacturer’s manual for recommended minimum
boiler supply temperatures.
This item is only available if there is at least one boiler set to auto
(Boiler Enable = AUTO) & non-condensing (Boiler Condense = NO).

90 to 225°F, OFF

(32.0 to 107.0°C, OFF)

Default: 200°F (93.0°C)

Access: ADV

BOILER MAXIMUM

The maximum allowed boiler target temperature.

PUMP or VALV

Default: PUMP

Access: ADV

PLANT FLOW

Selects whether each boiler is to use a pump or valve.

AUTO, 2 to 42°F

AUTO, 1.0 to 23.5°C

Default: AUTO

Access: ADV

BOILER DIFFERENTIAL

The temperature differential that the control is to use to cycle the boiler On & Off
(half above & half below the boiler target temperature).
This item is only available if Application Mode is set to either RSET, SETP, EMS
or BAS.

OFF, DMPR, DHWR

Default: OFF

Access: ADV

AUXILIARY RELAY

Selects the operation of the auxiliary relay to be either Combustion Air Damper
(DMPR) or DHW Recirculation Pump (DHWR).
If the External C.A. Proof / Off switch is set to External C.A. Proof, this setting is
fixed at DMPR.

OFF or AUTO

Default: AUTO

Access: ADV

PRIMARY PUMP 1

Selects whether primary pump 1 is operational or not.
This item is only available if Application Mode is set to either RSET, SETP, EMS
or BAS.

OFF or AUTO

Default: OFF

Access: ADV

PRIMARY PUMP 2

Selects whether primary pump 2 is operational or not.
This item is only available if Application Mode is set to either RSET, SETP, EMS
or BAS.

12 to 180 hr, OFF

Default: 96 hr

Access: ADV

ROTATE PRIMARY PUMPS

Sets the frequency of rotation of the primary pumps.
This item is only available if Application Mode is set to either RSET, SETP, EMS
or BAS & Primary Pump 1 & Primary Pump 2 is set to AUTO.

OFF, 0:10 to 20:00 min

Default: 0:20 min

Access: ADV

PRIMARY PUMP PURGE

Time the primary pump remains on once the appropriate calls (heat, setpoint or
DHW) are removed to purge heat from the boiler plant.
This item is only available if Application Mode is set to either RSET, SETP, EMS
or BAS & Primary Pump 1 or Primary Pump 2 is set to AUTO.

0:10 to 3:00 min

Default: 0:30 min

Access: ADV

FLOW PROOF DELAY

The time allowed for the control to receive a flow proof call once the primary
pump turns on.
This item is only available if the External Flow Proof / Off switch is set to External
Flow Proof.

0:10 to 3:00 min

Default: 1:00 min

Access: ADV

CA PROOF DELAY

The time allowed for the control to receive a C.A. proof call once the C.A. damper
(Aux) relay turns on.
This item is only available if the External C.A. Proof / Off switch is set to External
C.A. Proof.