Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual
Page 47

Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
47
Configuration Mode
Chapter 3
Table 23 - Communication Driver Properties
Field
Description
Valid Values
Serial Properties
Use Auto Config
Automatically or manually configures the baud rate, parity, and error checking
parameters.
Yes (auto configure)
No (manual configure)
Device
The serial device that the terminal is connected to.
PLC-5
®
, SLC
™, MicroLogix™, Logix
Platform
Error Check
Type of error checking used. Error checking is automatically configured if Use Auto Config
is set to Yes.
BCC, CRC
Parity
Type of parity used. Parity is automatically configured if Use Auto Config is set to Yes.
None, Odd, Even
Baud Rate
Data rate at which serial driver communicates. The baud rate is automatically configured
if Use Auto Config is set to Yes.
110, 300, 600, 1200, 4800, 9600,
19200, 38400, 57600, 115200
Stop Bits
Number of stop bits used.
1 or 2
Ack/Poll Timeout
Ack/Poll timeout value in ms.
20…60,000 ms
Max Retries
Number of retries before serial driver fails.
0…10
Station Number
Station number based on a specific device.
0…254
COM Port
Communication port used on the terminal.
1…4
DH-485 Properties
Jumper ID
Identifies the communication card if multiple cards are installed on the terminal.
0…3
Station Number
The unique station number of the terminal on the DH-485 network.
0…31 (decimal)
Baud Rate
The communication rate of the DH-485 network.
9600
19200
MaxStationNumber
The maximum station number on the DH-485 network. The value must be greater than or
equal to the Station Number.
0…31 (decimal)