Terminal does not start properly, Check for adequate power, Check indicators at startup – Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual
Page 144: Check start-up messages and codes

144
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Chapter 8
Troubleshooting
Terminal Does Not Start
Properly
This section provides general troubleshooting information to assist you when
trying to resolve problems during startup.
Check for Adequate Power
If a terminal does not receive adequate power, it can result in unpredictable
behavior. Refer to
DC Power Connections on page 28
for power requirements.
Check Indicators at Startup
When the terminal starts the FAULT and COMM indicators flash on and off,
then the COMM indicator flashes to signal progress during startup. When
startup is complete, the COMM indicator remains on, and is controlled by the
communication driver or application. The COMM indicator typically flashes
when communication is active.
The indicators are off if the terminal is not receiving power. Check the power
wiring and power supply.
If the indicators remain off, the power supply or logic board has failed. Check the
power wiring and power supply:
• If the power is not within range, replace the power supply.
• If the power is within range, replace the terminal.
shows indicator states if the terminal powers on and stops during
startup.
Check Start-up Messages and Codes
Maintenance Operations on page 151
for a list of message states and
error codes that can appear on the splash screen during startup.
Table 52 - Indicator States if Terminal Stops During Startup
FAULT (red)
Indicator
COMM (green)
Indicator
Description
Flashing
Off
Recoverable firmware error. Last firmware download failed.
Use the firmware upgrade wizard (FUW) to reload the firmware.
On
Off
Non-recoverable hardware fault with logic module:
• For 400 and 600 terminals, replace the terminal.
• For 1000 terminals, replace the logic module.
Blinking
Non-recoverable hardware fault with display module:
• For 400 and 600 terminals, replace the terminal.
• For 1000 terminals, replace the display module.