Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Chapter 8
Troubleshooting
4. Press the down arrow on the keyboard to select the following option:
Special BOOT Action -None
5. Press the right arrow three times to select the following option:
Special BOOT Action - Restore Factory Defaults
6. Press the up arrow to select ‘Reboot with selected options’.
7. Press Enter on your keyboard to initiate the factory default restore process.
The terminal is returned to its out-of-box state, including the firmware,
registry, file system, and storage areas. All user data is lost after the restore.
TIP
Use the keys at the bottom of window to make selections.
Initial Maintenance Window
default button pressed, please select maintenance options
Maintenance Menu -- ver 0x.xx
Special BOOT Action - None
Reboot with selected options
Continue with this system
boot.
This option will continue
booting with the options
selected on the left.
- IMPORTANT----------------------
USB keyboard required!
Press the RESET switch to
ignore changes and continue
system boot.
Maintenance Window with Restore Factory Defaults Selected
default button pressed, please select maintenance options
Maintenance Menu -- ver 0x.xx
Special BOOT Action - Restore Factory Defaults
Reboot with selected options
Selects the special BOOT
action that will be
executed during this system
boot.
- Restore Factory Defaults ----
All storage media that
exists on this terminal
will be restored to
a factory default state.
- IMPORTANT-------------------------
All customer updates will
be lost.