Restore factory defaults – Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual
Page 153
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
153
Troubleshooting
Chapter 8
3. With an option selected, press the right or left arrow keys to cycle through
the available operations or settings.
The result of each action is explained on the right.
4. Follow these steps, when done making selections.
a. Press the up arrow to return to
‘Reboot with selected options’.
b. Press the Enter key to continue booting.
Restore Factory Defaults
To recover from a firmware update failure, for example, fatal code 0F, you need to
restore your terminal to its out-of-box, factory default state.
Follow these steps to restore factory defaults from Maintenance mode.
1. Press and hold the DEFAULT switch on the back of the logic module.
2. Press and release the RESET switch.
3. Release the DEFAULT switch.
The maintenance menu is displayed.
Maintenance Window with Safe Mode Selected
default button pressed, please select maintenance options
Maintenance Menu -- ver 0x.xx
Special BOOT Action - SAFE Mode
Reboot with selected options
Selects the special BOOT
action that will be
executed during this system
boot.
- SAFE mode-------------------------
The system will start in the
configuration mode of
FactoryTalk View ME Station.
- IMPORTANT-------------------------
FactoryTalk View ME Station
will load at start up not
the custom HMI application.
The HMI application will
start normally the next
time the terminal is rebooted.
The version refers to the
boot loader.
TIP
Terminals require an attached USB keyboard to navigate in Maintenance mode.