109
Install and Replace Components
Chapter 5
4. If the communication module is attached, remove the four screws that
secure the communication module to the logic module and set the
communication module aside.
5. Loosen the four captive screws that secure the logic module to the display
module.
6. Carefully lift the logic module from the back of the display.
7. Install the new logic module and torque the four captive screws to
0.58 N•m (5…7 lb•in).
8. If necessary, install the communication module and torque the four screws
to 0.58 N•m (5…7 lb•in).
Install or Replace a
Communication Module
The communication module installs over the logic module. Communication
modules for the 1000 terminals are available as separate catalog numbers for field
installation.
Follow these steps to install a communication module.
1. Disconnect power from the terminal.
Communication Module
Display Module
Captive Screw
Screw
Logic Module
ATTENTION: Wear a properly grounded ESD wristband before touching
any of the electronic components in the logic module.
TIP
The logic module must be attached to the display module before you attach
the communication module.