Instance 2 attributes (polled i/o message) – Rockwell Automation 2705 RediSTATION Operator Interface User Manual User Manual
Page 50
Publication 2705-UM001A-EN-P
B-6 DeviceNet Information
Instance 2 Attributes (Polled I/O Message)
1
xxxxxx = node address
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
1
Get
State
USINT
0 = nonexistent
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
1 = I/O message
3
Get
Transport Class Trigger
USINT
82
hex
4
Get
Produced Connection ID
UINT
01111xxxxxx
binary
1
5
Get
Consumed Connection ID
UINT
10xxxxxx101
binary
1
6
Get
Initial Comm
Characteristics
USINT
01
hex
7
Get
Produced
Connection Size
UINT
1
8
Get
Consumed
Connection Size
UINT
1
9
Get/Set
Expected Packet Rate
UINT
0 msec (default),
with time resolution
of 10 msec
12
Get/Set
Watchdog Timeout Action
USINT
0 = timeout (default)
1 = auto delete
2 = auto reset
13
Get
Produced Connection
Path Length
UINT
6
14
Get
Produced Connection Path
Logical Segment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Structure of:
USINT
USINT
USINT
USINT
USINT
USINT
20
hex
04
hex
24
hex
01
hex
30
hex
03
hex
15
Get
Consumed Connection
Path Length
UINT
6
16
Get
Consumed Connection Path
Logical Segment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Structure of:
USINT
USINT
USINT
USINT
USINT
USINT
20
hex
04
hex
24
hex
02
hex
30
hex
03
hex